6 electrical characteristics (inverter output) – OPTI-UPS MD120L User Manual

Page 53

Advertising
background image

50 Chapter 5 Maintenance

50

7.6 Electrical Characteristics (Inverter Output)

Table 7-6 Inverter Output (to important load)

Rated

capacity(kVA)

Unit

6120KVA

Rated AC voltage

1

Vac

200/208(three-phase four-wire and sharing neutral with the

bypass)

Freqency

2

Hz

50/60

overload

105% load, long term operation

110% load, 1 hour

125% load, 10min

150% load, 1min

>150% load, 200ms

Fault current

340% short current limitation for 200ms

Non linear load

capability

3

100%

Neutral current

capability

170%

Steady state

voltage stability

±1(balanced load)

±2(100% imbalance load)

Transient voltage

response

4

±5

THD

<2(linear load) , <5(non linear load

3

)

Synchronization -

Window

Rated frequency ±2Hz(selectable: ±1~±5Hz)

Max change rate of

synch frequency

Hz/s

1: selectable: 0.1~5

Inverter voltage

range

%V(ac) ±5

Note:

1.

Factory setting is 208V. Commissioning engineers can set to 200V.

2.

Factory setting is 50Hz. Commissioning engineers can set to 60Hz.

3.

EN50091-3(1.4.58) crest ratio is 3: 1.

4.

IEC62040-3/EN50091-3 including 0%~100%~0% load transient, the recovery time is half

circle to within 5% of stable output voltage.

Advertising
This manual is related to the following products: