Chapter 1 Installation

19

1.7.9 LBS (Load Bus Synchronizer) Port

The dual bus system (DBS) consists of two independent UPS rack module systems, as shown in fig

1-20. The dual bus system is configured for high availability and is suitable for powering the load with

dual inputs. If the load is single-input load, the static transfer switch and LBS control is recommended to

maintain both UPS outputs synchronized for uninterrupted transfers. Please install the system according

to the installation descriptions for different system configurations.

The dual bus system is supported by UPS, it requires connecting the LBS signal cables of two UPS

when constructing the dual bus system; please refer to relevant chapter for detailed configuration and

installation, and the system software shall be configured as required.

UPS 1

LBS

监控旁路模块

UPS 2

LBS

监控旁路模块

Fig 1-20 LBS Connection Diagram

1.8 Installation Drawing

Please refer to fig 1-21, fig 1-22, fig 1-23 and fig 1-24:

Fig 1-21 Installation Diagram

UPS 1 monitoring
bypass module

UPS 2 monitoring
bypass module