Chapter 1 Installation

16

Position

Name

Purpose

J4.1

EPO_NC

EPO is activated when disconnecting fromJ4.2

J4.2

+24V

+24V, connect the common terminal of NC and NO

J4.3

EPO_NO

EPO is activated when shorting with J4.2

The EPO is triggered when shorting pin 2 and 3 or opening pin 2 and 1 of J4.

If an external emergency stop facility is required, it is connected via the reserved terminals of J4.

The external emergency stop facility needs to use shielded cables to connect to the normally

open/closed remote stop switch between these two pins. If this facility is not used, then pin 3 and pin 4 of

J4 must be open, or pin 1 and pin 2 of J4 must be shorted.

警告

危 险

Note

1. The emergency stop action within the UPS will shut down the rectifier, inverter and static bypass.

However, it does not internally disconnect the mains input power supply. To disconnect ALL power to

the UPS, open the upstream input circuit breaker(s) when the EPO is activated.

2. Pin 1 and 2 of J4 have been shorted before the UPS is delivered.

1.7.3 Generator Input Dry Contact

J5 is status interface for generator connection. Connect pin 2 of J5 with + 24V power supply, it

indicates that the generator has been connected with the system. The interface diagram is shown in fig

1-15, and interface description is shown in table 1-5.

J5

GEN

+24V

AUX-N.O.

AUX-N.O.

发电机

Fig 1-15 Diagram of status interface and connection of generator

Table 1-5 Description of maintenance bypass switch and output switch status interface

Position

Name

Purpose

J5.1

+24V

+24V power supply

J5.2

GEN

Connection status of generator

J5.3

GND

Power ground

1.7.4 BCB Input Port

J6 and J7 are the ports of BCB. The port diagram is shown in fig 1-16, and description is shown in

table 1-6.

Generator