6 integrated warning output dry contact interface – OPTI-UPS MD120L User Manual

Page 21

Advertising
background image

Chapter 1 Installation

18

J8

B

A

T

_

L

O

W

_

N

C

B

A

T

_

L

O

W

_

N

O

G

N

D

Fig 1-17 Battery warning dry contact interface diagram

Table 1-7 Battery warning dry contact interface description

Position

Name

Purpose

J8.1

BAT_LOW_NC

Battery warning relay (normally closed) will be open during warning

J8.2

BAT_LOW_NO

Battery warning relay (normally open) will be closed during warning

J8.3

GND

Center of battery warning relay

1.7.6 Integrated Warning Output Dry Contact Interface

J9 is the integrated warning output dry contact interface, when one or more than one present

warning is triggered, the system will send an integrated warning information, and provide an auxiliary

dry contact signal via the isolation of a relay. The interface diagram is shown in fig 1-18, and description

is shown in table 1-8.

J9

A

L

A

R

M

_

N

C

A

L

A

R

M

_

N

O

G

N

D

Fig 1-18 Integrated warning dry contact interface diagram

Table 1-8 Integrated warning dry contact interface description

Position

Name

Purpose

J9.1

ALARM_NC

Integrated warning relay (normally closed) will be open during warning

J9.2

ALARM_NO

Integrated warning relay (normally open) will be closed during warning

J9.3

GND

Centre of integrated warning relay

1.7.7 Mains Failure Warning Output Dry Contact Interface

J10 is the output dry contact interface for mains failure warning, when the mains fails, the system

will send a mains failure warning information, and provide an auxiliary dry contact signal via the isolation

of a relay. The interface diagram is shown in fig 1-19, and description is shown in table 1-9.