5 battery warning output dry contact interface, 6 integrated warning output dry contact interface, J6 j7 – OPTI-UPS MD120L User Manual

Page 74

Advertising
background image

Chapter 1 Installation

17

B

C

B

_

D

R

V

B

C

B

_

C

O

N

T

J6

J7

B

C

B

_

O

N

L

+24V

+24V

+24V

Fig 1-16 BCB Port

Table 1-6 Description of BCB port

Position

Name

Description

J6.1

BCB_DRV

BCB actuating signal, provide the actuating signal of +18V, 20mA

J6.2

BCB_CONT BCB contact status, connect with the normally open signal of BCB

J7.1

GND

Power ground

J7.2

BCB_ONL

BCB on-line

–input (normally open) , BCB is on-line when the signal

is connecting with GND

1.7.5 Battery Warning Output Dry Contact Interface

J8 is the output dry contact interface, which outputs the battery warnings of low or excessive

voltage, when the battery voltage is lower than set value, an auxiliary dry contact signal will be

provided via the isolation of a relay. The interface diagram is shown in fig 1-17, and description is

shown in table 1-7.

J8

B

A

T

_

L

O

W

_

N

C

B

A

T

_

L

O

W

_

N

O

G

N

D

Fig 1-17 Battery warning dry contact interface diagram

Table 1-7 Battery warning dry contact interface description

Position

Name

Purpose

J8.1

BAT_LOW_NC

Battery warning relay (normally closed) will be open during warning

J8.2

BAT_LOW_NO

Battery warning relay (normally open) will be closed during warning

J8.3

GND

Center of battery warning relay

1.7.6 Integrated Warning Output Dry Contact Interface

J9 is the integrated warning output dry contact interface, when one or more than one present

warning is triggered, the system will send an integrated warning information, and provide an auxiliary

dry contact signal via the isolation of a relay. The interface diagram is shown in fig 1-18, and description

is shown in table 1-8.