Chapter 1 Installation

4

Chapter 1 Installation

This chapter introduces the installation of MD series UPS (hereby referred to as UPS), including

initial checking, sitting, positioning, cabling and installation drawings.

1.1 Introduction

This chapter introduces the relevant requirements for positioning and cabling of the UPS.

As each site has its requirements, this chapter provides step-by-step installation instructions, which

acts as a guide to the general procedures and practices that should be observed by the installing

engineer.

警告

危 险

Warning-Installation can only be done by authorized engineers

1. Do not apply electrical power to the UPS equipment before the approval of commissioning

engineer.

2. The UPS should be installed by a qualified engineer in accordance with the information contained

in this chapter.

警告

危 险

Note: 3-Phase 4-Wire Input Power is required

The standard UPS can be connected to TN, TT and IT AC distribution system (IEC60364-3) of

3-phase 5-wire

警告

危 险

WARNING: battery hazards

SPECIAL CARE SHOULD BE TAKEN WHEN WORKING WITH THE BATTERIES ASSOCIATED

WITH THIS EQUIPMENT. When connecting the battery, the battery terminal voltage will exceed

400Vdc and is potentially lethal.

Eye protection should be worn to prevent injury from accidental electrical arcs.

Remove rings, watches and all metal objects.

Only use tools with insulated handles.

Wear rubber gloves.

If a battery leaks electrolyte, or is otherwise physically damaged, it must be replaced, stored in a

container resistant to sulfuric acid and disposed of in accordance with local regulations.

If electrolyte comes into contact with the skin, the affected area should be washed immediately

with water.

1.2 Initial Checking

Perform the following checking operations prior to the UPS installation.

1.

Visually examine if there is any damage inside and outside the UPS rack and battery equipment

due to the transportation. Report any such damage to the shipper immediately.

2.

Verify the product label and confirm the correctness of the equipment. The equipment label is

attached on the back of front door. The UPS model, capacity and main parameters are marked on

the label.