Chapter 1 Installation

12

1.5 Protective Devices

For safety concerns, it is recommended to install external circuit breakers or other protective devices

for the input AC supply of the UPS system. This section provides generic practical information for

qualified installation engineers. The installation engineers should have the knowledge of the regulatory

wiring standards, and of the equipment to be installed.

1.5.1 Rectifier and Bypass Input Supply of the UPS

Install suitable protective devices in the distribution unit of the incoming mains supply, considering

the power cable current-carrying capacity and overload capacity of the system. Generally, the magnetic

circuit breaker with IEC60947-2 tripping curve C (normal) at the 125% of the current listed in table 1-2 is

recommended.

警告

危 险

Note

For IT power network system, 4-pole protective device must be installed on the external input

distribution of the UPS.

If protection against earth faults (RCD devices) is required for the upstream of the input supply, the

installed device should:

 Sensitive to DC unidirectional pulses (class A) in the network

 Insensitive to transient current pulses

 Have an average sensitivity that is adjustable between 0.3A~1A

The RCCB must be sensitive to DC unidirectional pulses (class A) in the network, while insensitive

to transient current pulses, as shown in fig 1-10 respectively.

Fig 1-10 RCCB sign

1.5.2 Battery

A battery unit is composed of 40 batteries connected in series, a centreline is drawn from in

between (the joint part between the 20

th

and 21

st

battery), plus the line drawn from the front and back,

there are altogether 3 lines connected with UPS line contact bank. The battery line must push through a

DC circuit breaker before connecting to corresponding UPS line contact bank. The detailed wiring please

refer to fig 1-11 below:

Fig 1-11 Diagram of batteries connected in series

40 batteries connected in series