Chapter 1 Installation

15

connected to DRY terminal must be separated from power cables. Moreover, these cables should be

double insulated with a typical 0.5 to 1.5 mm

2

cross-section area for a maximum connection length

between 25 and 50 meters.

1.7.1 Dry Contact Interface of Battery and Environmental Temperature Detection

The input dry contact J2 and J3 can detect the temperature of batteries and environment

respectively, which can be used in environment monitoring and battery temperature compensation 1.

J2 and J3 interfaces diagram are shown in fig 1-13, the description of interface is in table 1-3.

J2

J3

T

E

M

P

_B

A

T

T

E

M

P

_E

N

V

Fig 1-13 Diagram of J2 and J3 dry contact for temperature detecting

Table 1-3 Description of input dry contact interface J2 and J3

Position

Name

Purpose

J2.1

TEMP_BAT

Battery temperature detection

J2.2

GND

Power ground

J3.1

TEMP_ENV

Environment temperature detection

J3.2

GND

Power ground

Note: Specified temperature sensor is required for temperature detection (R25=5Ohm,

B25/50=3275), please confirm with the manufacturer, or contact local maintenance engineers when

placing an order.

1.7.2 Remote EPO Input Port

The UPS has an Emergency Power OFF (EPO) function. This function can be activated by pressing

a button on the control panel of the UPS or through a remote contact provided by the user. The EPO

pushbutton is protected by a hinged plastic cover.

J4 is the input port for remote EPO. It requires shorting NC and +24v during normal operation, and

the EPO is triggered when opening NC and +24v, or shorting NO and +24v. The port diagram is shown in

fig 1-14, and port description is shown in table 1-4.

J4

E

P

O

_

N

C

+

2

4

V

E

P

O

_

N

O

+24V

Fig 1-14 Diagram of input port for remote EPO

Table 1-4 Description of input port for remote EPO