Chapter 1 Installation

13

1.5.3 UPS Output

A main output switch has been installed in UPS, the user shall install the over current protective

device on the bypass of each output of the external distribution cabinet.

1.6 Power Cables

Design the cables according to the descriptions in this section and local regulatory wiring standards,

and the environmental conditions should be taken into consideration. Refer to IEC60950-1 Table 3B.

警告

危 险

Warning

Prior to cabling the UPS, confirm the status and positions of the switches of the UPS rectifier input

power supply / bypass power supply and mains power distribution board.

Ensure that these switches are opened and attached with WARNING label so as to prevent

unauthorized operation to these switches.

1.6.1 Maximum stable state current and configuration of cable system

Maximum stable state current and configuration of cable system, please refer to table 1-2.

Table 1-2 Maximum stable state current and configuration of cable system

System Name

MD60-10

MD90-15 MD120-20 MD100-10

MD150-15

MD200-20

Capacity

System

capacity

60kVA

90kVA

120kVA

100kVA

150kVA

200kVA

Module

capacity

10kVA

15kVA

20kVA

10kVA

15kVA

20kVA

Cabinet

dimension

600*900*1600(W*D*H mm)

600*900*2000(W*D*H mm)

Main

Input

Rated

current A

101

153

203

169

255

338

Cable mm

2

35

50

75

50

75

90

Output

Rated

current A

90

136

180

150

227

300

Cable mm

2

25

35

50

50

75

75

Battery

Rated

current A

119

180

239

200

298

399

Cable mm

2

35

50

75

75

75

90

PE

Cable mm

2

35

50

75

75

75

90

警告

危 险

Warning

FAILURE TO FOLLOW ADEQUATE EARTHING PROCEDURES CAN RESULT IN EMI, ELECTRIC

SHOCK HAZARD OR RISK OF FIRE.

1.6.2 Cable Connection

警告

危 险

Note

Advertising