2 bypass module, 2 operation mode – OPTI-UPS MD120L User Manual

Page 81

Advertising
background image

24 Chapter 2 Operations

24

Fig 2-1 System principle framework

2.1.2 Bypass Module

The circuit blocks labeled “bypass module” in fig 2-1 contain electronically controlled switching

circuits that enable the critical load to be connected to either the inverter output or to a bypass power

source via the static bypass line. During normal system operation the load is connected to the inverter;

but in the event of a UPS overload or inverter failure, the load is automatically transferred to the static

bypass line.

To provide a clean (no-break) load transfer between the inverter output and static bypass line, the

inverter output and bypass supply must be fully synchronized during normal operating conditions. This is

achieved through the inverter control electronics, which makes the inverter frequency track that of the

static bypass supply, provided that the bypass remains within an acceptable frequency window.

A manually controlled maintenance bypass supply is incorporated into the UPS design. It enables

the critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine

maintenance.

警告

危 险

Note

When the UPS is operating in bypass mode or on maintenance bypass, the connected equipment is

not protected from power failures or surges and sags.

2.2 Operation Mode

The MD UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these

modes:

 Normal mode

Advertising
This manual is related to the following products: