3.6 Standards

ELECTRICAL SAFETY REGULATIONS

IEC 60664-1 Insulation of low voltage equipment
IEC 61010-1 Electrical safety
IEC 62053-21 Active energy meters (class 1 and 2)
UL 94 Enclosure flammability test
VDE 110 Low voltage equipment insulation

ELECTROMAGNETIC COMPATIBILITY

IEC 61000-3-2 , IEC 61000-3-3 , IEC 61000-6-4 , EN 55011 , EN 55022 , IEC 61000-6-2 ,
IEC 61000-4-2 , IEC 61000-4-3 , IEC 61000-4-4 , IEC 61000-4-5 , IEC 61000-4-8
IEC 61000-6-1 , IEC 61000-4-11 , ENV 50141.

HOUSING SYMBOLS

Maximum input voltage 400 V

Reinforced insulation

Product manufactured with recyclable and reusable material. Do not dispose with

domestic wastes. At the end of its lifespan, deposit the product at a specific collection point
meant for electrical or electronic devices. REI-RAEE record (ES) Nº: 3338.

Please contact the after sales service or technical service of CIRCUTOR, S.A. in case you have
a question about the unit's operation or you have detected a fault.

4

FEATURES OF CIR-e

3

The CIR-e³ analyzer is a programmable measurement unit that measures, calculates and
records
the main electrical parameters of single and three-phase industrial networks in its
memory. We must highlight the following concepts:

Serial number: The serial number of CIR-e³ is an important parameter, since all files generated
by the unit must be identified with that number. The 10-digit serial number is written on the rear
features label of CIR-e³.

Programming: The unit is programmed with the setup software CIR-e.exe. The application is
stored in the SD card supplied with the unit. In addition, the card records the electrical
parameters that are sent to the Web server.

Display (in Cir-e³ Web): The measurement unit includes the right of use of the associated
software that is required to handle the energy data of the CIR-e³ Web application. It is located in
a web site that is active 24 hours a day, 365 days a year:

http://cir-e3.circutor.com

.

Installation: The analyzer can be installed to analyze balanced (3 wire) or unbalanced (4 wire)
single and three-phase networks. The unit must be powered with the auxiliary power supply
cables in any of the connection options. The auxiliary power supply wires of the unit are Brown
and Green.

Measurements: The analyzer takes 128 samples per cycle of the voltage and current variables
in true root mean square (TRMS). With all of the samples taken, the unit calculates the
arithmetic mean during the recording period selected by the user. The analyzer also records the
maximum and minimum values measured during each period. To take these measurements, the
analyzer has four voltage sensor inputs and three current sensor inputs.