Voltage measurement and current connection – CIRCUTOR CDP-0 User Manual

Page 14

Advertising
background image

CDP

14

Instruction Manual

Table 8: Configuration of the external CVM Mini.

Configuration of the external CVM Mini.

Parameter

Value

Peripheral number

Configurable

Bauds

Configurable

Bits

8

Parity

NO

Stop bits

1 Stop bit

It is recommended that a category 5e FTP cable or higher is used and a twisted
pair must be used for each earth leakage signal pair.

3.5.3. VOLTAGE MEASUREMENT AND CURRENT CONNECTION

The CDP measures current using the MC1 or MC3 transformers with a
secondary current of 250 mA

Table 9: Current measurement transformer models.

Transformer models

MC3 – three-phase

transformer

MC1- 1 transformer per phase

Models 63, 125 and 250 A.

Models:
150/200/250A, 250/400/500A,
50/100/150A, 500/1000/1500A,
1000/1500/2000 A
Each transformer has 3 ratio ranges,
changing a connection cable and the
chosen ratio in the measuring unit.