CDP

32

Instruction Manual

Disconnection condition:

𝑷𝑷𝑷𝑷𝑷

∑ 𝑷𝑷𝑷𝑷𝑷𝑷𝑷𝑷𝑷𝑷 𝑷𝑷𝒓𝒓𝒓𝒓 < 𝑀𝒓𝒂. 𝑷𝑷𝑷𝑷 𝑷𝑷𝑷𝑷𝑷𝑷𝒐𝒐𝑷𝑷𝑷𝑷


(

0

8000

= 0%)  0% ≤ 50% 

this condition is met

relay 2 stays connected



At this point, the CDP-G will check whether it can connect the third load. To do
so, it must verify whether the connection condition is met:

Condition 1:

𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃

𝑃𝑃𝑃𝑃𝑃𝑃𝑃𝑃 𝑃𝑃𝑖𝑃𝑖𝑖𝑃𝑖

𝑥 100 ≤ 𝑀𝑚𝑥. 𝑃𝑃𝑃𝑃𝑚𝑚𝑖𝑚𝑃𝑃 𝑖𝑚𝑚𝑃𝑃


(

8000

10000

𝑥 100 = 80%)  80% ≤ 90%  this condition is met


Condition 2:

-If Injection Margin = 0%

 It checks whether:

Pgrid < 2 x (0.03) x Pconsumed

-If Injection Margin

≠ 0%  It checks whether:

Pgrid < 2 x Injection Margin x Pconsumed


0 < 2 x 0.03 x 8000

 this condition is met

If the 2 conditions are met, the relay closes and connects load number 3.

(Figure 29)