Figure 71: Setup web site: Auxiliary load relays (Manual).

You can manually activate each relay by pressing the corresponding button for
each one.

If you select dynamic management of the loads (

Figure 72

), you have to program

the following parameters:

Figure 72: Setup web site: Auxiliary load relays (Dynamic).


Max. modulation value: In this section you enter the maximum modulation

value and can add dynamic loads to the system below.

Connection Order: Select how you are going to connect the relays: By pri-

ority or rotating


1st/2nd/3rd Priority: If you have selected priority connection, you will then

select the priority for each of the relays.


Max. grid contribution: In this section you enter the value for maximum grid

contribution, which is the minimum value for deactivating loads.


Reconnecting time: Minimum time to allow system stabilisation between:

- the activation of two loads.
- the deactivation of two loads.
- the deactivation of the last load and the activation of a new one.