Control, Figure 68 – CIRCUTOR CDP-0 User Manual

Page 51

Advertising
background image

CDP

Instruction Manual

51

Binary: this option allows 16 regulation stages between 0% and 100% of the
inverter's nominal power. The relay combinations are done using binary logic.

When the Binary option is activated, relay number 4 stops functioning
as a protection against reverse current and starts functioning like the
rest of the relays.


Figure 68: Setup web site: detail of the inverter section.

If the SMA option is selected, the Inverter X S/N,

Figure 69

parameter will

appear on the screen, where you will need to enter the serial numbers of
each of the inverters.
It is important to enter the serial number of each inverter in the phase in
which it was installed, so that the device can detect it.

Figure 69:

Setup web site: detail of the Inverter section (SMA).

Inverter power: Total power to be controlled by the CDP. (in the event of two

2000 W inverters, enter 4000 W).

The power limit is 1 MW.

Number of inverters: number of inverters to control.

6.1.2.2. Control
Inverter control parameters:
Phase: the architecture of the inverter grid connection must be selected. The

available options are:

Single phase: single-phase installation with single-phase inverters.
Three phase: three-phase installation with three-phase inverters.

Three single phases: three-phase installation with three single-phase
inverters

.