Data logger, Analyzers setup – CIRCUTOR CDP-0 User Manual

Page 56

Advertising
background image

CDP

56

Instruction Manual

Relay 1, Relay 2, Relay 3: Configuration of the relays.

- Power : Power to be consumed by the load. If it is zero, the load is
considered to be deactivated.
- Min. connection time: Minimum time that a load must stay connected
before it can be deactivated, if required.

6.1.2.5. Data logger
(see

6.2.1. CDP AS A DATA

LOGGER

)

Time between logs: time to record logs in the Data Logger: 1, 5, 10, 15

or 60 minutes.

6.1.3. Analyzers setup

It is also possible to configure the communications between the CDP and the
CVM Mini or CVM Net power analyzers (

Figure 73

) on the web site.

Figure 73: Setup web site: Analyzers setup.

6.1.3.1. Load analyzer

Enable external analyzer: facilitates the use of an external analyzer rather

than the CDP as a measuring unit.

Primary current: primary value of the load analyzer of the current

transformer.


Device number: Peripheral number of the external analyzer.

(Only activated when the “Enable external analyzer” option is activated).

6.1.3.2. Grid analyzer

Primary current: primary value of the grid analyzer of the current

transformer.

Device number: peripheral number of the CVM power analyzer installed to

measure the consumption of the grid.



Advertising
This manual is related to the following products: