Communications, Configuration, Site – CIRCUTOR CDP-0 User Manual

Page 46: Via web

Advertising
background image

CDP

46

Instruction Manual

6.- COMMUNICATIONS


The unit has two web sites:

 Configuration web site.
 Display web site.

6.1. CONFIGURATION WEB SITE


The CDP can be used to configure the parameters of the

Table 15

, via Web.

Table 15: Configuration parameters.

Description

Units

Default

value

Inverter type

-

Fronius

Inverter power

W

1

Number of inverters

-

1

Work mode configuration

-

Single-phase

Activate compensation

-

0

No injection threshold

%

3

Permitted power to be injected

%

0

Activate the management of non-critical loads

-

disabled

Maximum modulation value

%

50

Relay connection order

-

Priority

Maximum grid contribution value

%

25

Minimum reconnection time

Minutes

5

Power to be consumed by each of the loads connected
to the relays

W

-

Minimum time that the load must stay connected

Minutes

15

Activate reverse current relay

-

1

Grid injection validation time

Seconds

0

Reconnection time

Seconds

0

Maximum number of reconnections

-

0

Reconnection period

Seconds

0

Time between datalogger logs

Minutes

15

Activate external unit to measure the user's current

-

0

Transformation ratio for the current of L1 (Channel for
measuring the user's current in single-phase mode)

A/250 mA

1

Peripheral number address
(External unit activated)

-

-

Transformation ratio for the current of L2 (Channel for
measuring the grid's current in single-phase mode)

A/250 mA

1

Peripheral number address

-

1

Activate external unit to measure the inverter's current

-

0

Transformation ratio for the current of L3 (Channel for
measuring the inverter's current in single-phase mode)

A/250 mA

1

Peripheral number address (External unit activated)

-

2

Communication speed with the grid analyzers.

Bauds

19200