6.1.2. Power control & Data logger

In this part,

Figure 67

, five groups of parameters are displayed:

 Those related to the model and number of inverters: Inverter.

 Those related to inverter control: Control.
 Those related to the operation of the reverse current control relay:

Reverse current relay.

 Those related to managing non-critical loads: Auxiliary load relays.
 That related to the data log generated: Data logger.

Figure 67: Setup web site: Power control & Data logger.


6.1.2.1. Inverter

In this section you can select:
Inverter type: Inverter model to be used in the installation. All inverters

connected to the CDP must be of the same type.

If you select the option Generic 4 inputs, the parameter Mode appears on the
screen with two possible options (

Figure 68

):

Discrete: this option allows 4 regulation stages: 0%, 30%, 60% and 100%.