Condition switches, Voltage difference, Condition switches -3 – Basler Electric BE1-25 User Manual

Page 13: Voltage difference -3, Figure 1-1. voltage monitor acceptance zones -3

Advertising
background image

Figure 1-1. Voltage Monitor Acceptance Zones

Condition Switches
Five Condition Switches are located on the Voltage Monitor Card, each with two positions to select ON

(Down) and OFF (Up). When ON, Condition Switch No. 1 programs the relay to require recognition that

the line and bus are not in an overvoltage condition (NOT OV) before the SYNC output is allowed.

Condition Switches No. 2 through No. 5 modify the voltage monitor response according to a programmed

set of external conditions. The possible external conditions for each of these four switches are:

Switch 2.

Live Line/Live Bus (LL-LB)

Switch 3.

Dead Line/Live Bus (DL-LB)

Switch 4.

Live Line/Dead Bus (LL-DB)

Switch 5.

Dead Line/Dead Bus (DL-DB)

When a selected condition has been recognized, the voltage monitor circuit may be instructed to

immediately energize the Sync-Check output relay, or (if provided) the Voltage Monitor output relay. (See

Figure 1-1, Note 1.)
See Table 2-1, callout S, for a complete description and precautions on setting the Conditions Switches.

The location of the switches is shown in Figure 2-2.

Voltage Difference
A voltage monitor is available that checks the phasor or average voltage difference between the two

inputs. This can be used to prevent the closure of a generator breaker if the voltage difference is too great

(even if the phase angle and voltage level monitoring circuits indicate that proper closing conditions are

otherwise present).
The voltage difference option (included with option 2-A, 2-B, 2-C, 2-R, 2-T or 2-U) is typically used to

reduce the amount of possible system shock or transients when closing a breaker. This option compares

the voltage between line and bus against a selected limit, and initiates either an enable or an inhibit signal

for the sync-check logic, thereby narrowing the voltage across the breaker contacts (as compared to a

simple sync-check acting alone). Figure 1-2 shows closing zones obtained by combining phasor voltage

difference, phase angle limit, and line and bus live/dead voltage limits. Figure 1-3 shows closing zones

obtained by combining average voltage difference, phase angle limit, and line and bus live/dead voltage

limits.

LL ADJ

=100V

DL / OV ADJ

=40V

LINE

DEAD

LINE VOLTAGE

LIVE

135V (MAX)

100V

50V

10V (MIN)

2

LIVE LINE/

LIVE BUS

CONDITION

4 OV

135V (MAX)
100V

50V

10V (MIN)

P0004-36

BUS

1

DEAD LINE/

LIVE BUS

CONDITION

LIVE

DB / OV ADJ

=120V

LB ADJ

=35V

BUS VOLTAGE

60V FIXED MINIMUM VOLTAGE

LIMIT (LIVE LINE/LIVE BUS

CONDITION SYNC-CHECK

3

NOTES:

SYNC RELAY CONTACTS

CLOSED BY VOLTAGE MONITOR

SYNC-CHECK LOGIC ENABLED

2

1

LOGIC

4 OV EXCEEDED, SYNC-CHECK

TO ON PERMITS

LOGIC NOT ENABLED (SETTING

MODE SWITCH NO. 1 TO ON

AND CONDITION SWITCH NO. 1

FUNCTION ONLY)

OV)

3

3

9170200990 Rev U

BE1-25 General Information

1-3