SPECIFICATIONS

Voltage and Phase Sensing Nominally rated at 60 hertz with a range of 45 to 65 hertz at a

maximum burden of 1 VA per phase to 125% of nominal voltage.

Maximum continuous voltage rating is 160% of nominal.

Contact Sensing

User-supplied contacts with a minimum rating of 0.05 ampere at

250 Vdc are required at all contact sensing inputs. (Specifically the

52b input, the optional expandable phase angle window, and the

optional external voltage condition switches.)

Sensing circuit current is supplied by the relay when isolated

sensing is selected. Non-isolated sensing requires an externally

applied dc sensing voltage equal to the nominal voltage of the

relay power supply input.

Contact Sensing Burden

For Power Supply Option O ...... 2.4 VA

For Power Supply Option P ....... 6.25 VA

For Power Supply Option R ....... 1.2 VA

For Power Supply Option T…….12.5 VA

Power Supply

One of the four types of power supplies listed in Table 1-1 may be

selected to provide internal relay operating power.

Table 1-1. Power Supply

Type

Input Voltage

Burden at Nominal

Nominal

Range

O (mid range)

48 Vdc

24 to 150 Vdc

1.5 W

P (mid range)

125 Vdc

120 Vac

24 to 150 Vdc

90 to 132 Vac

1.8 W

10.5 VA

R (low range)

24 Vdc

12 to 32 Vdc ∗

1.6 W

T (high range)

250 Vdc

240 Vac

68 to 280 Vdc

90 to 270 Vac

2.1 W

17.4 VA

Type R power supply may require 14 Vdc to begin operation. Once operating, the voltage may be

reduced to 12 Vdc.

CAUTION

If contact sensing is isolated (style number Mxxxxxx5xxx), external voltage

should not be applied to the contact sensing inputs. Applying voltage to the

contact sensing inputs will result in damage to the relay.

9170200990 Rev U

BE1-25 General Information

1-9