Basler Electric BE1-25 User Manual

Page 29

Advertising
background image

Callout

Control or Indicator

Function

R

MODE Switch No. 1 (Bus)

MODE Switch No. 2 (Line)

For Both Mode Switches:

Up = NORMAL Mode;

Down = NOT OV Mode.

When in the NORMAL Mode:

(1) A high voltage threshold is established by front panel

controls, above which the bus (or line, as the case may

be) is considered live;

(2) A low voltage threshold is established by front panel

controls, below which the bus (or line) is considered dead.

When in the NOT OV Mode:

(1) A voltage above the high voltage setpoint setting is

considered overvoltage.

(2) A voltage below the low voltage setpoint setting is

defined as dead.

(3) A voltage between the two setpoints is defined as live.

This condition is indicated by the illumination of two LEDs:

either LL or LB and the corresponding NOT OV.

S

CONDITION Switches

No. 1 (Not-Overvoltage

Enable to the sync logic

circuitry)

Up = OFF: Disables the NOT OV Mode of operation

during a live line/live bus condition.

Down = ON: Allows the NOT OV Mode of operation to

add a further constraint to the live line/live bus condition

(assuming that the NOT OV Mode has been previously

selected on Mode Switch No. 1 or No. 2). The additional

constraint is that the line and/or bus must not be in the

overvoltage region. (This switch does not affect the

Voltage Monitor Output relay.)

9170200990 Rev U

BE1-25 Controls and Indicators