Not ov testing, Not ov testing -7, Table 5-2. not overvoltage mode testing -7 – Basler Electric BE1-25 User Manual

Page 63

Advertising
background image

NOT OV Testing
Step 6.
Test the NOT OV Mode of the Voltage Monitor as follows. (Proceed to step 7 if this mode is not

used.)

(a) Adjust the following front panel controls by applying the voltages stated below, adjusting each

control to the threshold where its LED indicator just turns ON. (Reference callouts L, N, F,

and G of Figure 2-1).

LB:

Adjust to 80 Vac.

DB/NOT OV: Adjust to 120 Vac.

LL:

Adjust to 80 Vac.

DL/NOT OV: Adjust to 120 Vac.

(b) Set TIME DELAY to 99 seconds. This allows the convenience of using in-phase voltages for

testing non-synchronous functions (without unwanted SYNC outputs).

(c) Apply simulated line and bus voltages adjusted to check the bus and line voltage criteria

given in Table 5-2. To be valid, an output must occur immediately after line and bus voltages

are applied.

Step 7. If the voltage difference option is furnished, check for proper enabling of the Sync-Check output

contacts when the voltage differential between line and bus is within selected ∆V settings.

Step 8. If the expand phase angle option is furnished, check that the phase window widens by a factor of

2 or 3 (according to the position of the jumper on the Sync-Check PC board) when the expand

phase input terminal is closed.

Table 5-2. NOT OVERVOLTAGE Mode Testing

No output∗ throughout voltage range. (Normal SYNC output function still operates. SYNC output occurs

after 99 seconds time delay if the line and bus voltages are greater than 60 Vac. This 60 Vac corresponds

to the minimum voltage requirement for the sync-check function, not the LL and LB settings.) For the

following tests, if your unit has a minimum voltage requirement of less than 60 Vac, use a voltage that is

appropriate for your unit.

Condition Switch

1

Up

2

Up

3

Up

4

Up

5

Up

Mode Switch

1

Down

2

Down

Output∗ only when bus input voltage is greater than 60 volts but less than 120 volts, and line is less than

60 volts.

Condition Switch

1

Up

2

Up

3

Down

4

Up

5

Up

Mode Switch

1

Down

2

Down

Output∗ only when bus input voltage is less than 60 volts and line is greater than 60 volts but less than

120 volts.

9170200990 Rev U

BE1-25 Testing

5-7

Advertising