Basler Electric BE1-25 User Manual

Page 28

Advertising
background image

Callout

Control or Indicator

Function

L

LB Indicator

LB Adjustment

Red LED lights when bus voltage exceeds the reference

voltage established by the LB setting that defines a live

bus condition.

Continuously adjustable over a range of 10 to 135 Vac.

Adjustment is by small screwdriver through an access

hole in the front panel. CW rotation increases voltage

setting.

M

V Indicator

Red LED lights whenever the (optional) Voltage Monitor

Output relay is energized.

N

DB/NOT OV Indicator

When in the NORMAL Mode:

Red LED lights when the bus voltage is less than the

reference voltage established by the DB/NOT OV setting

that defines a dead bus condition.

When in the NOT OV Mode:

Red LED lights when the bus voltage does not exceed the

reference voltage established by the DB/NOT OV setting

that defines an overvoltage condition.

DB/NOT OV Adjustment

Continuously adjustable over the range of 10 to 135 Vac.

Adjustment is by small screwdriver through an access

hole in the front panel. CW rotation increases the voltage

setting.

O

PHASE ANGLE Selector

NOTE

A PHASE ANGLE setting of 00 inhibits

operation of the relay.

Thumbwheel switches set the acceptable maximum

phase difference between the line and bus voltages. This

phase difference window is adjustable in 1° increments

over a range of 01° to 99°.

P

PHASE ANGLE Indicator

Red LED lights when the phase angle is within the limits

established by the adjacent PHASE ANGLE Selector.

Q

Switchable jumper for

EXPAND option

Position of jumper in Figure 2-2 controls the width of the

expanded phase angle window as a multiple of the

PHASE ANGLE setting. The two positions are X2 and X3.

2-4

BE1-25 Controls and Indicators

9170200990 Rev U

Advertising