Basler Electric BE1-25 User Manual
Page 31
Callout
Control or Indicator
Function
S
(Cont’d)
No. 4 (Live Line/Dead
Bus)
Up = OFF
If relay has Output Option E or F:
The ON (Down) position causes immediate closure of the
Sync Output contact, if a live line/dead bus condition is
detected with the breaker open.
If relay has Output Option G or H:
The ON (Down) position causes immediate actuation of
the Voltage Monitor relay, if a live line/dead bus condition
is detected with the breaker open.
No. 5 (Dead Line/Dead
Bus)
Up = OFF
If relay has Output Option E or F:
The ON (Down) position causes immediate closure of the
Sync Output contact if a dead line/dead bus condition is
detected with the breaker open.
If relay has Output Option G or H:
The ON (Down) position causes immediate actuation of
the Voltage Monitor relay if a dead line/dead bus condition
is detected with the breaker open.
9170200990 Rev U
BE1-25 Controls and Indicators