Figure 3-1. Functional Block Diagram

Minimum Voltage Detection
Minimum voltage detection circuitry enables the TIME DELAY timer when both line and bus are within

operating range of the relay. Voltage sensing circuits are guaranteed to operate at a minimum voltage of

60 volts. They are guaranteed not to operate at voltages less than 20 volts. Some units may operate at

voltages in between these two levels because of the individual characteristics of specific components.

Minimum voltage detection is usually in the range of 45 to 55 volts.

Contact Sensing Options
Before any relay output can occur, there must be an initiating signal from external contacts. Contact

sensing circuitry allows the relay to monitor circuit breaker status (52b) and various conditions selected by

the user. (Contact requirements are provided in the Specifications.)
In any sync-check relay, all of the contact sensing inputs supplied must use one of two methods.

1. Isolated sensing (Option 1-5), uses current supplied by the relay to monitor the isolated contacts.

2. Non-isolated sensing (Option 1-4), monitors an external dc source whose nominal voltage is

equal to the input to the BE1-25 power supply.

Power Supply
Operating power for the relay circuitry is supplied by a wide range, electrically isolated, low-burden power

supply. Power supply operating power is not polarity sensitive. The front panel power LED and power

supply status output indicate when the power supply is operating. Power supply specifications are listed in

Table 1-1.

Power Supply Status Output Option
The power supply status output relay (Option 3-6) has normally closed (NC) output contacts. The relay is

energized upon power-up, thus opening its contacts. The contacts will remain open as long as normal

relay operating voltage is maintained. However, if the power supply voltage falls below the requirements

for proper operation, the power supply status output relay de-energizes, thus closing the NC output

contacts.

01-30-01

D1058-04.vsd

OPERATING

POWER

BUS

LINE

EXPAND

PHASE

ANGLE

OPTION

OPTIONAL

EXTERNAL

CONTACTS

LB

DB OR BOV

LL

DL OR LOV

52b

POWER

SUPPLY

CROSS

ZERO

ZERO

CROSS

PHASE

DIFFERENCE

MEASUREMENT

POWER

-2 OR -3

JUMPER

ON PCB

TO INTERNAL

CIRCUITRY

AND

AND

OR

POWER

SUPPLY

SENSOR

PHASE

ANGLE

SELECTOR

COMPARATOR

AND

AND

TIMER

TIME DELAY

SWITCHES

PHASE

SYNC.

OUTPUT

SYNC.

OUTPUT

AUX.

OUTPUT

P.S. STATUS

ISOLATION

MINIMUM

VOLTAGE

DETECTION

ISOLATION

FILTER

ISOLATION

FILTER

FRONT PANEL SETTINGS

PEAK OR AVG

DETECTOR

V

LL LB IF MODE 1:
(LL OV)(LB OV) IF MODE 2

LB

DB OR BOV

LL

DL OR LOV

VOLTAGE

MONITOR

SELECTION

LOGIC

MODE

SWITCHES

CONDITION

SWITCHES

MONITOR
ACCEPT

PATHS

ALTERNATE

MONITOR

VOLTAGE

OUTPUT

OPTION

DEPENDING

VOLT.

SYNC-CHECK CIRCUITRY

VOLTAGE MONITOR OPTIONS

.

.

.

ON OUTPUT

PEAK OR AVG

DETECTOR

PEAK OR AVG

DETECTOR

PEAK OR AVG

DETECTOR

PEAK OR AVG

DETECTOR

3-2

BE1-25 Functional Description

9170200990 Rev U

Advertising