Basler Electric BE1-25 User Manual

Page 21

Advertising
background image

Line and Bus Voltage

Monitor Option

Range

Continuously adjustable over the range of 10 to 135 Vac.

Accuracy

The line and bus voltage setpoints do not vary more than 3% from

a reference measurement at 25°C, with nominal input frequency,

and with temperature and voltage inputs within specified operating

range. Setpoints do not vary more than 1% from a reading at 25°C

over the limited temperature range of +15 to +40°C.

Isolation

In accordance with IEC 255-5 and IEEE C37.90, one minute dielectric

(high potential) tests as follows:
All circuits to ground: 2,121 Vdc
Input to output circuits: 1,500 Vac or 2,121 Vdc

Surge Withstand Capability

Oscillatory

Fast Transient

Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability

(SWC) Tests for Protective Relays and Relay Systems.

Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability

(SWC) Tests for Protective Relays and Relay Systems.

Radio Frequency

Interference (RFI)

Maintains proper operation when tested for interference in

accordance with IEEE C37.90.2-1987, Standard Withstand

Capability of Relay Systems to Radiated Electromagnetic

Interference from Transceivers.

UL Recognition

UL recognized per Standard 508, UL File No. E97033. Note:

Output contacts are not UL recognized for voltages greater than

250 V.

Shock

In standard tests, the relay has withstood 15 G in each of three

perpendicular planes without structural damage or degradation of

performance.

Vibration

In standard tests, the relay has withstood 2 G in each of three

mutually perpendicular axes swept over the range of 10 to 500

hertz for a total of six sweeps, 15 minutes each sweep, without

structural damage or degradation of performance.

Operating Temperature

40°C (–40°F) to 70°C (158°F).

Storage Temperature

65°C (–85°F) to 100°C (212°F).

GOST-R Certification

GOST-R certified per the relevant standards of Gosstandart of Russia.

Weight

13.7 (6.2 kg) pounds maximum.

Case Size

S1 (Refer to Section 4 for case dimensions.)


9170200990 Rev U

BE1-25 General Information

1-11

Advertising