Basler Electric BE1-25 User Manual

Page 30

Advertising
background image

Callout

Control or Indicator

Function

S

(Cont’d)

No. 2 (Live Line/Live Bus)

Up = OFF

Down = ON

When ON (Down), the Voltage Monitor Output relay is

actuated when a live line/live bus condition is recognized.

CAUTION

If relay has Output Option E or F:

Condition Switch No. 2 (LL-LB) must be Up

(OFF) when output option E or F is selected.

Otherwise, sync outputs will occur under live

line/live bus conditions without benefit of the

Sync-Check function. No switch or contact

should be connected to the LL-LB input

terminal in this case.

CAUTION

If relay has Output Option G or H:

Condition Switch No. 2 (LL-LB) may be Down

(ON) only when output option G or H has been

selected and the Voltage Monitor Output

contacts do not by-pass the Sync-Check

contact. Use of the external LL-LB switch (if

installed) is similarly limited.

No. 3 (Dead Line/Live

Bus)

Up = OFF

If relay has Output Option E or F:

The ON (Down) position causes immediate closure of the

Sync Output contact, if a dead line/live bus condition is

detected with the breaker open.

If relay has Output Option G or H:

The ON (Down) position causes immediate actuation of

the Voltage Monitor relay, if a dead line/live bus condition

is detected with the breaker open.


2-6

BE1-25 Controls and Indicators

9170200990 Rev U