Vent configurations, Installation – Montigo 30FID Traditional User Manual

Page 13

Advertising
background image

Page 13

XG00516-

150204

I-Series Indoor Gas Fireplace

Installation

Figure 1 Sec.3

Vent Configurations

This appliance can only be vented vertically. The minimum vent

height measured from the floor under the unit to the bottom of the

termination is 10’. The maximum height that a vent can extend is

36’. This unit uses 3” x 3” Co-linear venting. This is a direct vent

unit and as such requires that both intake and exhaust vents are

connected and operational. Using existing chases as a partial vent

mechanism is not allowed. Due care is required to ensure that all

vent components are properly connected and sealed. Care must

also be taken when installing flashing or termination caps to make

sure that the structure of the building cannot be subject to water

penetration. Proper roofing and chimney finishing techniques

must be used.

Steps for vent connection

** Before installing the venting system, make sure that any dampers

or baffle plates in the fireplace are removed or do not present any

hindrance to your installation **
1). Determine the length of flex venting that will be required. Cut

2 lengths a couple of feet longer than you anticipate needing. The

length of these needs to be determined after the vent is stretched

out. Flex venting generally comes compressed and needs to be

stretch out to meet the lengths as specified.

2). From the roof, attach the Vent Lengths to the Adaptor. Don`t

forget to have the Flashing placed between the Flex Vent and the

Adaptor before attaching the Flex Vent.

3). Using commercial grade sealant around the perimeter of the

Collars of the Adaptor, use a minimum of 3 Tech screws in each Vent.

4). Install the Termination to the top of Adaptor. Use a minimum of

4 tech screws to attach the Termination to the Adaptor.

5). Feed the Flex Venting down the chimney until the Adaptor is

situated near the top of the Chimney. Use a commercial grade of

sealant between the Flashing and the Chimney top. Fasten the

Flashing to the top of the Chimney using a fastening method that

will properly secure the flashing permanently.

6). Attach the Adaptor to the top of the Flashing using 4 tech

screws. Seal around the perimeter of the Adaptor where it meets

the Flashing.

7). From inside the house check how long the vents protrude into

the Fireplace. Read the section on installation where fuel supply

pressure checking needs to be done. This procedure can be

done at this point by installing the venting to the appliance prior

to pushing the appliance into the fireplace cavity.

8). Once pre-installation steps have been completed, trim the vent

length to the correct length for installation. The Correct length will

leave the Flue Collar Slide Plate suspended around 18-19 inches

from the floor of the Fireplace.

9). Remove the Flue Collar Slide Plate from the appliance. Attach

both flex ends to the Flue Collar Slide plate. Use a commercial high

temp sealant around the Flue Collars on Flue Collar Slide Plate

before installing the Venting. Use a minimum of 3 tech screws to

properly secure the Venting to the Flue Collar Slide Plate.

** Make certain that the Exhaust and Intake Vents are connected

to the correct collars on the Flue Connection Plate. If they

are connected in reverse, this unit will not operate and re-

installation will be necessary. **

Termination 46DVA-VCH

Adaptor 46DVA-GK

Flex Liner VT15FL3

Hearth / Floor

Masonry Chimney

(Cut-away View)

Exhaust Flue

Intake Flue

Flashing

Fireplace Insert

Advertising
This manual is related to the following products: