VCM & VCM-X Controllers

SMTS II Technical Guide

26

VCM & VCM-X Confi guration

VCM-X Confi guration

Touch the

< Confi guration>

button to access the

Confi guration Setpoints Screens.

For screens that contain radio buttons, touch the radio but-

ton next to your selection. For screens with square buttons, touch one or
more square buttons to make your confi guration selections for the unit.

HVAC Mode Enable Source

Touch the radio button to select the Temperature Sensor that will deter-
mine the Heating, Cooling, or Vent Mode of operation. The available
selections are as follows:

 

Supply Air Temperature

—This is typical for VAV

applications. Occupied Cooling with Morning Warm-up.

Outdoor Air Temperature

This is for 100% Outdoor

Air (MUA) units. Dehumidifi cation utilizing a Dewpoint

Calculation if equipped with an Outdoor Air Humidity

Sensor.

Space Temperature

—This is for any unit that conditions

a space and is not 100% Outdoor air. Occupied/Unoccu-

pied Heating, Cooling, and Vent Modes of operation.

Return Air Temperature

—This selection can be used

when an Average Building Temperature (the Return Air

Temperature) needs to determine Heating, Cooling, and

Vent Modes of operation.

Supply Air w/ Supply Air Tempering

—This selection is

for VAV “cooling only” applications where because of cold

outdoor temperatures, even at minimum damper position,

you may need to enable heat to maintain the cooling near its

Cooling Supply Air Setpoint. When heat is enabled during

this sequence, it will control to a non-adjustable setpoint

that is 2ºF less than the Cooling Supply Air Setpoint.

Config

Figure 35: VCM-X Confi guration Screen 1

HVAC Reset Source

The Supply Air Heating and Cooling Temperature Setpoints can be reset
using various input sources. Default is No Reset. Touch the radio button
to select the desired Reset Source for Supply Air Temperature Reset.
The Single Zone VAV option should be selected in applications where
the Supply Fan VFD speed is reset based on the Space Temperature. If
you select No Reset, then neither the Supply Air Setpoint nor Supply
Fan VFD Reset will occur. The available selections are as follows:

 

No Reset

 

Space Temperature

Return Air Temperature

External Analog Input

Fan VFD Signal Percentage

Outdoor Air Temperatur

Single Zone VAV

Single Zone VAV w/ CV Heat

Setpoints for Unit 0102

Configuration

Reset Source

No Reset

Page 2 of 14

Single Zone VAV

Space Temperature

Return Air Temperature

External Analog Input

Fan VFD Signal Percentage

Outdoor Air Temperature

Single Zone VAV w/CV Heat

Figure 36: VCM-X Confi guration Screen 2

Revised 4/21/15