Vcm, vcm-x & vcb-x controllers, Vcb-x controllers, Vcb-x static & staging delay setpoints – Orion System System Manager TS II In-House User Manual

Page 56: Smts ii technical guide 56, Zone

Advertising
background image

Zone

Zone

VCM, VCM-X & VCB-X Controllers

SMTS II Technical Guide

56

VCB-X Controllers

Setpoints for Unit 0001

Outdoor CFM Intake Area

0.00

Sq Ft

Exhaust CFM Area

Supply CFM Area

0.00

0.00

Static & Air Setpoints

Sq Ft

Sq Ft

Return CFM Area

Page 4 of 4

Sq Ft

0.00

Figure 106: VCB-X Static & Air Setpoints Screen 4

Outside CFM Intake Area

For the controller to properly calculate the Outside Air CFM, you need
to enter the inside area (sq. ft.) of the Outdoor Air Duct/Damper. When
measuring the Outdoor Air Damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accu-
rate to 2 decimal places. High limit = 200 sq. ft.; Low limit = 0 sq. ft.;
Default = 0 sq. ft.

Exhaust CFM Area

For the controller to properly calculate the Exhaust Air CFM, you need
to enter the inside area in square feet of the Exhaust Air duct/damper.
When measuring the Exhaust Air damper area, be sure to measure the
inside dimensions of the damper. The duct size needs to be accurate to
two decimal places. The more accurate the measurements, the more
accurate the CFM reading will be. High limit = 200 sq. ft.; Low limit =
0 sq. ft.; Default = 0 sq. ft.

Supply CFM Area

For the controller to properly calculate the Supply Air CFM, you need
to enter the area in square feet of the Supply Air Duct/Damper. When
measuring the Supply Duct Damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accurate
to 2 decimal places. High limit = 200 sq. ft.; Low limit = 0 sq. ft.

Return CFM Area

For the controller to properly calculate the Return Air CFM, you need
to enter the area in square feet of the Return Air Duct/Damper. When
measuring the Return Air Damper area, be sure to measure the inside
dimensions of the damper. The more accurate the measurements, the
more accurate the CFM reading will be. This value needs to be accu-
rate to 2 decimal places. High limit = 200 sq. ft.; Low limit = 0 sq. ft.;
Default = 0 sq. ft.

Staging Delays Setpoints

Touch the

< Staging Delays>

button to access the Staging

Delays Setpoint Screens.

Cooling Stage Up Delay Time

This is the amount of time that must elapse between each Compressor
activation to prevent all Compressors from activating at the same time
due to large cooling demands. High limit = 15 minutes; Low limit = 3
minutes; Default = 3 minutes.

Cooling Stage Down Delay Time

This is the amount of time that must elapse between each Compressor
deactivation to prevent all Compressors from deactivating at once as
the cooling demand decreases. High limit = 15 minutes; Low limit = 1
minute; Default = 1 minute.

Cooling Minimum Run Time

This is the minimum amount of time the Compressors must remain on
once they have been activated. This overrides the Stage Down Delay if
that is not as long as this delay. High limit = 15 minutes; Low limit = 5
minutes; Default = 5 minutes.

Cooling Minimum Off Time

Once a Compressor has been staged back off, it must remain off for this
amount of time to prevent short cycling. High limit = 15 minutes; Low
limit = 3 minutes; Default = 3 minutes.

Mod Cooling Time Period

The Mod Cooling Time Period is the delay before another Modulating
Cooling Signal increase or decrease can be made and is user-adjustable.
Short Mod Cooling Time Periods may cause hunting of the Modulat-
ing Cooling Signal. This is the rate at which the Modulating Cooling
Signal is calculated. High limit = 240 seconds; Low limit = 5 seconds;
Default = 30 seconds.

VCB-X Static & Staging Delay Setpoints

Staging

Setpoints for Unit 0001

Cooling Stage Up Delay Time

Cooling Minimum Off Time

Mod Cooling Time Period

3

3

30

Min

Cooling Stage Down Delay Time

Cooling Minimum Run Time

1

5

Staging Delays

Min

Min

Min

Min

Page 1 of 5

Figure 107: VCB-X Staging Delay Setpoints Screen 1

Advertising
This manual is related to the following products: