SMTS II Technical Guide

VCM, VCM-X & VCB-X Controllers

61

VCB-X Controllers

VCB-X Miscellaneous Setpoints

Building Pressure Control High Volts

Voltage at which the control signal for Building Pressure is increasing
the pressure by the maximum amount. High limit = 10 VDC; Low limit
= 0 VDC; Default = 10 VDC.

Building Pressure Control Low Volts

Voltage at which the control signal for Building Pressure is lowering the
pressure by the maximum amount. High limit = 10 VDC; Low limit =
0 VDC; Default = 0 VDC.

Single Zone VAV Integral

If the Single Zone VAV Fan Speed Control requires integral control, enter
the Integral Constant here. High limit = 10; Low limit = 0; Default = 0.

Leaving Water Calibration Offset

If the Leaving Water Temperature Sensor is reading incorrectly, you can
use this option to enter an offset reading to adjust the Sensor’s Sensitivity.
Enter a positive Sensor Calibration to increase the Leaving Water Tem-
perature Sensor reading or a negative value to lower the Sensor reading.
High limit = 100 PPM; Low limit = -100 PPM; Default = 0 PPM.

CO2 Sensor Calibration Offset

If the CO

2

Sensor is reading incorrectly, you can use this option to enter

an offset reading to adjust the Sensor’s Sensitivity. Enter a positive Sen-
sor Calibration to increase the CO

2

Sensor reading or a negative value

to lower the Sensor reading. High limit = 500 PPM; Low limit = -500
PPM; Default = 0 PPM.

Space Sensor Calibration Offset

If the Space Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Space Temperature
Sensor reading and a negative value to lower the Sensor reading. High
limit = 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC; Default = 0ºF / 0ºC.

Supply Sensor Calibration Offset

If the Supply Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Enter a positive Sensor Calibration value to raise the
Supply Air Temperature Sensor reading and a negative value to lower
the Sensor reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF /
-55.5ºC; Default = 0ºF / 0ºC.

Outdoor Sensor Calibration Offset

If the Outdoor Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset temperature to adjust the Sensor’s
Temperature. Enter a positive Sensor Calibration value to raise the
Outdoor Air Temperature Sensor reading and a negative value to lower
the Sensor reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF /
-55.5ºC; Default = 0ºF / 0ºC.

Return Sensor Calibration Offset

If the Return Air Temperature Sensor is reading incorrectly, you can
use this option to enter an offset reading to adjust the Sensor’s Sensi-
tivity. Enter a positive Sensor Calibration value to raise the Return Air
Temperature Sensor reading and a negative value to lower the Sensor
reading. High limit = 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC;
Default = 0ºF / 0ºC.

Coil Temperature Calibration Offset

If the Coil Temperature Sensor is reading incorrectly, you can use this
option to enter an offset reading to adjust the Sensor’s Sensitivity. Enter
a positive Sensor Calibration value to raise the Coil Temperature Sensor
reading and a negative value to lower the Sensor reading. High limit
= 100ºF / 55.5ºC; Low limit = -100ºF / -55.5ºC; Default = 0ºF / 0ºC.

Setpoints for Unit 0001

Building Pressure Control High Volts

10

Building Pressure Control Low Volts

Single Zone VAV Integral

0

Miscellaneous

VDC

Page 5 of 6

Leaving Water Calibration Offset

0

0

Deg

VDC

PPM

0

C 2 Sensor Calibration Offset

O

Figure 116: VCB-X Miscellaneous Setpoints Screen 5

Setpoints for Unit 0001

Space Sensor Calibration Offset

0

Supply Sensor Calibration Offset

Outdoor Sensor Calibration Offset

0

Miscellaneous

Page 6 of 6

Return Sensor Calibration Offset

0

0

Deg

0

Coil Temperature Calibration Offset

Deg

Deg

Deg

Deg

Deg

Figure 117: VCB-X Miscellaneous Setpoints Screen 6