VCM, VCM-X & VCB-X Controllers

SMTS II Technical Guide

48

VCB-X Controllers

VCB-X Confi guration

Morning Warm-Up

Touch the radio button to select type of Morning Warm-Up control.
Default is None.



None

— There is no Morning Warm Up required.

 

Stand Alone Warm-up Control

The VCB-X Controller

is not communicating to Orion VAV Box controls, but a

Morning Warm Up Relay can be confi gured to signal boxes

by other to open.

 

Warm-up w/Broadcast to Fixed Airfl ow—

The VCB-X

Controller is communicating to Orion VAV Boxes and will

broadcast a command to the boxes to go to a Fixed

Percentage Position or Airfl ow while in Morning Warm Up.

This

fi xed position is confi gured in the VAV box controller.

 

Warm-up w/Broadcast to Maximum Airfl ow—

The

VCB-X Controller is communicating to Orion VAV Boxes

and will broadcast a command to the boxes to go to a

Maximum Percentage Position or Airfl ow while in Morning

Warm Up. This maximum position is confi gured in the VAV

box

controller.

Setpoints for Unit 0001

Configuration

Morning Warm-Up

Page 15 of 19

None

Stand Alone Warm-up Control

Warm-up w/Broadcast to Fixed Airflow

Warm-up w/Broadcast to Maximum Airflow

Figure 88: VCB-X Relay Confi guration Screen 15

Setpoints for Unit 0001

Configuration

Binary Input Configuration

Page 16 of 19

Emergency Shutdown Input is Required

Proof of Flow Input is Required

Dirty Filter Input is Required

Defrost Coil Switch Installed

Figure 90: VCB-X Relay Confi guration Screen 17

Binary Input Confi guration

Touch the square button to select the binary inputs on the VCB-X
Controller.

Emergency Shutdown Input is Required

Select this item for YES if a Smoke Detector/Firestat
or other Emergency Shutdown input is connected to the
Emergency Shutdown binary input. If a Shutdown condition
occurs and the 24V signal is removed from this input, the
Supply Fan and Heating and Cooling Relay Outputs will be
de-energized and an alarm will be generated. Default is NO.

Proof of Flow Input is Required

Select this item if the unit is equipped with a Proof of Flow
Switch and it is connected to the VCB-X. If selected as
YES and the Proof of Flow Switch is open, only the Supply
Fan Relay will be active. If any other relays such as Heating
Stages or Cooling Stages are active, they will be deactivated
when the Proof of Flow Switch input is lost. Default is NO.

Dirty Filter Input is Required

Select this item if a Dirty Filter switch is connected to the
Dirty Filter binary input. If the Dirty Filter input is active,
an alarm will be generated. Default is NO.

Defrost Coil Switch Installed

Select this item if a Defrost Coil Temperature Switch is
installed and is connected to the Defrost Coil Temperature
Switch binary input. If this switch closes, it will initiate a
Defrost Mode. Default is NO.

Setpoints for Unit 0001

Configuration

Morning Cool-Down

Page 16 of 20

None

Stand Alone Cool-Down Control

Cool-Down w/Broadcast to Fixed Airflow

Cool-Down w/Broadcast to Maximum Airflow

Figure 89: VCB-X Relay Confi guration Screen 16

Morning Cool-Down

Touch the radio button to select type of Morning Cool-Down control.
Default is None.



None

— There is no Morning Cool Down required.

 

Stand Alone Cool-Down Control

The VCB-X

Controller is not communicating to Orion VAV Box

controls, but a Morning Cool Down Relay can be

confi gured to signal boxes by other to open.

 

Cool-Down w/Broadcast to Fixed Airfl ow—

The

VCB-X Controller is communicating to Orion VAV Boxes

and will broadcast a command to the boxes to go to a Fixed

Percentage Position or Airfl ow while in Morning

Cool-Down.

This

fi xed position is confi gured in the VAV

box

controller.

 

Cool-Down w/Broadcast to Maximum Airfl ow—

The

VCB-X Controller is communicating to Orion VAV Boxes

and will broadcast a command to the boxes to go to a

Maximum Percentage Position or Airfl ow while in Morning

Cool-Down. This maximum position is confi gured in the

VAV box controller.