SMTS II Technical Guide

VCM, VCM-X & VCB-X Controllers

49

VCB-X Controllers

Setpoints for Unit 0001

Configuration

Monitor Return Airflow Sensor

Monitor Supply Airflow Sensor

Monitor Exhaust Airflow Sensor

Monitor Outdoor Airflow Sensor

Control Outdoor Airflow

Has Outdoor Air Temperature Sensor

Page 17 of 19

Ebtron Sensors

Paragon Sensors

Figure 91: VCB-X Relay Confi guration Screen 18

Installed Sensors

Touch the square button to select the desired airfl ow sensor monitoring:

Monitor Return Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Return Air airfl ow stream of this unit

. Default is NO.

Monitor Supply Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Supply Air airfl ow stream of this unit

. Default is NO.

Monitor Exhaust Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Exhaust Air airfl ow stream of this unit

. Default is NO.

Monitor Outdoor Airfl ow Sensor—

Select

this item if

you have an Airfl ow Monitoring station

measuring the CFM

of the Outdoor Air airfl ow stream of this unit

. Default is NO.

Control Outdoor Airfl ow—

Select

this item if

you have an Airfl ow Monitoring station and are controlling the

OA Damper to an airfl ow (CFM) setpoint. Default is NO.

Has Outdoor Air Temperature Sensor—

Select

this

item if you have any type of Outdoor Air Temperature Sensor

installed.

Type of Monitoring Station

Touch the radio button to select the type of airfl ow monitoring station:

 

EBTRON Sensors

—Select this item if using an Ebtron or

Greentrol Airfl ow Monitoring Station.

 

Paragon Sensors

—Select this item if using a Paragon

Airfl ow Monitoring Station.

VCB-X Confi guration

Setpoints for Unit 0001

Configuration

Broadcast Outdoor Air Humidity

Broadcast Outdoor Air Temperature

Broadcast Commands to VAV Boxes

Broadcast Building Pressure

Page 18 of 19

Figure 92: VCB-X Relay Confi guration Screen 19

Setpoints for Unit 0001

Configuration

Page 19 of 19

Glycol Percentage for Water Source Heat Pumps

0% 32.0 Deg Freezing Point

5% 29.1 Deg Freezing Point

10% 26.1 Deg Freezing Point

15% 22.9 Deg Freezing Point

20% 19.2 Deg Freezing Point

25% 14.7 Deg Freezing Point

30% 9.2 Deg Freezing Point

35% 2.4 Deg Freezing Point

40% -6.0 Deg Freezing Point

Figure 93: VCB-X Relay Confi guration Screen 20

Broadcast Outdoor Air Humidity—

The VCB-X will

broadcast its Outdoor Air Humidity Reading to other HVAC

units if they are not equipped with their own Outdoor Air RH

sensors. A network communications device (MiniLink PD or

CommLink) is needed in order for this feature to operate.

Broadcast Outdoor Air Temperature—

The VCB-X will

broadcast its Outdoor Air Temperature Reading to other HVAC

units if they are not equipped with their own Outdoor Air

Temperature sensors. A network communications device

(MiniLink PD or CommLink) is needed in order for this feature

to

operate.

Broadcast Commands to VAV Boxes—

The VCB-X will

broadcast all applicable information and commands to the VAV

Boxes.

Broadcast Building Pressure—

The VCB-X will broadcast

Building Pressure from this unit to any other unit requiring this

value.

Glycol Percentage for Water Source Heat Pumps

Select the percentage that applies to your unit.