Vcm, vcm-x & vcb-x controllers, Vcb-x controllers, Vcb-x temperature setpoints – Orion System System Manager TS II In-House User Manual

Page 52: Smts ii technical guide 52, Zone

Advertising
background image

Zone

Zone

VCM, VCM-X & VCB-X Controllers

SMTS II Technical Guide

52

VCB-X Controllers

Cooling Reset Source High Limit

If a SAT Reset Source has been confi gured, then the Cooling Mode
Supply Air Setpoint will be reset to its minimum limit (Supply Air
Cooling Setpoint) as the reset source rises to this level. If this unit has
been confi gured for Single Zone VAV operation, then the Supply Fan
VFD will be reset towards 100% as the Space Temperature rises towards
this setpoint. High limit = 150ºF / 65.55ºC; Low limit = 1ºF / -17.20ºC.
Default = 75ºF / 24ºC.

Cooling Reset Source Low Limit

If a SAT Reset Source has been confi gured, then the Cooling Mode Sup-
ply Air Setpoint will be reset to its maximum limit (Supply Air Cooling
Reset Limit) as the reset source drops to this level. If this unit has been
confi gured for Single Zone VAV operation, then the Supply Fan VFD
will be reset towards the Cooling Minimum Fan VFD Signal Setpoint
as the Space Temperature falls towards this setpoint. High limit = 150ºF
/ 65.55ºC; Low limit = -10ºF / -23.30ºC. Default = 70ºF / 21ºC.

Cooling Staging Window

When the VCB-X Controller is in Cooling Mode, if the Supply Air
Temperature drops below the Active Supply Air Cooling Setpoint mi-
nus the Cooling Staging Off Deadband value, a Cooling Stage will be
deactivated after its Minimum Run Time. High limit = 30ºF / 16.66ºC
(no offset); Low limit = 1ºF / 0.55ºC; Default = 5ºF / 2.8ºC.

Cooling Outdoor Air Lockout

If the Outdoor Air Temperature drops below this level, the Mechanical
Cooling is locked out. High limit = 100ºF / 37.77ºC; Low limit = -30ºF
/ -34.44ºC; Default = 50ºF / 10ºC.

Cooling Minimum Fan VFD Signal

If this unit is confi gured for Single Zone VAV operation, the Cooling
Minimum Fan VFD Signal will be the fan speed at which the VFD will
start operating at when cooling is initiated. It can then modulate up to
100% as the space temperature rises within the range created by the
Cooling Reset Source Low Limit and the Cooling Reset Source High
Limit. If this is a CAV unit this should be set to 100%. High limit =
100%; Low limit = 0%; Default = 30%.

VCB-X Temperature Setpoints

Cooling Low Temperature Cutoff

The VCB-X controller will temporarily disable Cooling if while in Cool-
ing Mode, the Supply Air Temperature drops below this Cooling Low
Temperature Cutoff Setpoint. The unit will restart when the Supply Air
Temperature has risen 5º above this level. See the VCB-X Controller
Field Technical Guide
for detailed information on the Low and High
Supply Air Temperature Cutoff sequence of operation. High limit =
100ºF / 37.77ºC; Low limit = 0ºF / -17.77ºC; Default = 40ºF / 4.50ºC.

Mod Cooling Proportional Window

The Modulating Cooling Window is the control range of the Modulating
Signal above and below the Active Supply Air Temperature Setpoint. The
larger the Modulating Cooling Window, the smaller the signal adjust-
ment per Time Period will be for each 1ºF the Supply Air Temperature
is from the Active Supply Air Temperature Setpoint. If the Supply Air
Temperature is this amount away from the SAT setpoint, 10% of the
possible output signal will be applied. High limit = 30ºF / 16.66ºC; Low
limit = .1ºF / .055ºC; Default = 10ºF / 5.55ºC.

Supply Air Heating Setpoint

If No Reset has been confi gured for the SAT Reset Source, then this
setpoint will be the Heating Mode Supply Air Setpoint. If a Reset Source
has been confi gured, then this setpoint will be the lowest temperature
the Supply Air Setpoint can be reset to. High limit = 240ºF / 115.55ºC;
Low limit = 40ºF / 4.50ºC; Default = 120ºF / 48ºC.

Supply Air Heating High Reset Limit

If a SAT Reset Source has been confi gured, then this is the maximum
that the Heating Mode Supply Air Setpoint can be reset up to. High limit
= 250ºF / 121.11ºC; Low limit = 0ºF / -17.77ºC; Default = 120ºF / 48ºC.

Heating Reset Source High Limit

If a SAT Reset Source has been confi gured, then the Heating Mode
Supply Air Setpoint will be reset to its minimum limit (Supply Air Heat-
ing Setpoint) as the reset source rises to this level. If this unit has been
confi gured for Single Zone VAV operation, then the Supply Fan VFD
will be reset towards the Heating Minimum Fan VFD Signal Setpoint as
the Space Temperature rises towards this setpoint. High limit = 150ºF /
65.55ºC; Low limit = 1ºF / -17.22ºC. Default = 75ºF / 24ºC.

Setpoints for Unit 0001

Cooling Staging Window

Cooling Low Temperature Cutoff

Mod Cooling Proportional Window

5

40

10

°F

Cooling Outdoor Air Lockout

Cooling Minimum Fan VFD Signal

50

60

°F

°F

°F

°F

Temperatures

Page 6 of 9

Figure 99: VCB-X Temperature Screen 6

Setpoints for Unit 0001

Supply Air Heating Setpoint

Heating Reset Source Low Limit

Supply Setpoint Reset Loop Rate

85

70

30

°F

Supply Air Heating High Reset Limit

Heating Reset Source High Limit

85

75

°F

°F

°F

°F

Temperatures

Page 7 of 9

Figure 100: VCB-X Temperature Screen 7