SMTS II Technical Guide

VCM, VCM-X & VCB-X Controllers

55

VCB-X Controllers

VCB-X Static & Air Setpoints

Static Pressure Setpoint

For VAV units, a Supply Fan VFD or Bypass Damper Actuator is used to
maintain the Duct Static Pressure Setpoint. The Static Pressure Output
Signal varies to control to the Static Pressure Setpoint. The Duct Static
Pressure is maintained at this setpoint anytime the Main Fan is running.
High limit = 3.00”WG; Low limit = 0.10”WG; Default = 1.50”WG.

Static Setpoint Deadband

The Duct Static Setpoint accuracy is controlled by this value. No
Main Fan VFD changes are made if the static is within this range of
this setpoint. High limit = 0.50”WG; Low limit = 0.01”WG; Default
= 0.10”WG.

Building Pressure Setpoint

The Building Pressure is maintained at this setpoint while the Main Fan
is running. See detailed explanation that follows. High limit = 0.20”WG;
Low limit = -0.20”WG; Default = 0.02”WG.

Building Setpoint Deadband

The Building Pressure Setpoint accuracy is controlled by this value. No
Relief Fan VFD changes are made if the pressure is within this range
of this setpoint. See detailed explanation that follows. High limit =
0.10”WG; Low limit = 0.01”WG; Default = 0.01”WG.

Building Pressure Control

The VCB-X can maintain Building Static Pressure anytime the Supply
Fan is operating. A Building Pressure Transducer must be connected to
the VCB-X EM1 Expansion Module. The following are the available
control options.

Direct Acting Building Pressure Control

On/Off Exhaust Fan

If an On/Off Exhaust Fan is

being used, a relay output must be confi gured for

“Exhaust Fan”. This relay will energize whenever the

Building Pressure rises above the Building Pressure

Setpoint by the Deadband amount. The relay will de-

energize when the Building Pressure falls below the

Building Pressure Setpoint by the Deadband amount.

Exhaust Fan VFD or Modulating Exhaust

Damper

If confi gured for Modulating Exhaust, a user-

adjustable voltage output (AOUT1 – Building Pressure

Output on the VCB-X EM1 Expansion Module) will

be used to control this fan or damper. An Exhaust Relay

can be confi gured if necessary to enable the fan or

damper. Whenever the Building Pressure rises above

the Building Pressure Setpoint by the Deadband amount,

the Exhaust Fan Relay will energize and the Modulat-

ing Signal will activate to control to the Building

Pressure Setpoint. If the Building Pressure falls below

the Building Pressure Setpoint by the Deadband amount,

the Modulating Signal will modulate towards 0% as it

attempts to maintain the Building Pressure Setpoint.

The Exhaust Fan Relay is energized whenever the

Modulating Signal is above 0%.

Reverse Acting Building Pressure Control

Outdoor Air Damper

If this option is confi gured,

the VCB-X will use the user-adjustable Economizer/

Outdoor Air Damper output signal (AOUT2 –

Economizer Control Signal) to maintain the Building

Pressure Setpoint. Whenever the Building Pressure

falls below the Building Pressure Setpoint by the

Deadband amount, the modulating Economizer Output

Signal will modulate the damper open to control to

the Building Pressure Setpoint. If the Building Pressure

rises above the Building Pressure Setpoint by the

Deadband amount, the damper will modulate towards

closed as it attempts to maintain the Building Pressure

Setpoint. When this option is selected, no Economizer

free cooling or CO

2

IAQ operation will be available.

Supply Fan VFD

– Contact WattMaster regarding this

Reverse Acting Building Pressure Control option. It

should not be used in most applications. If this option

is selected, the user-adjustable Supply Fan VFD Output

(AOUT1 on the VCB-X) will be used to control the

Supply Fan VFD to maintain the Building Pressure

Setpoint in similar fashion to the Outdoor Air Damper

control described above.

Setpoints for Unit 0001

Static Pressure Setpoint

Building Pressure Setpoint

1.50

0.02

Wg

Static Pressure Deadband

Building Setpoint Deadband

0.10

0.01

Static & Air Setpoints

Wg

Wg

Page 3 of 4

Wg

Figure 105: VCB-X Static & Air Setpoints Screen 3