VCM, VCM-X & VCB-X Controllers

45

VCB-X Controllers

Dehumidifi cation Control

Touch the radio button to select the type of Dehumidifi cation control.
Default is None.

None

—The unit does not have a Dehumidifi cation Mode.

Dehumidify in Occupied Vent Mode Only

—The unit

can only enter Dehumidifi cation during the Occupied Vent

Mode (when there is no call for Cooling or Heating).

Dehumidify in Vent Mode Anytime

—The unit can only

enter

Dehumidifi cation during the Vent Mode (when there

is no call for Cooling or Heating) in both the Occupied and

Unoccupied

operation.

Dehumidifi cation in All Modes Occupied

—This is

Occupied

Mode

Dehumidifi cation Priority. The unit can

enter

Dehumidifi cation during Cooling, Heating, or Vent

Modes, but only while in Occupied operation.

Dehumidifi cation in All Modes Anytime

This is

Occupied and Unoccupied Dehumidifi cation Priority. The

unit can enter Dehumidifi cation during Cooling, Heating, or

Vent Modes while in Occupied or Unoccupied operation.

For units controlled by space humidity sensors, Dehumidifi cation is
initiated based on an Indoor Humidity Setpoint. For 100% OA units
(MUA), Occupied Dehumidifi cation is initiated based on an Outdoor Air
Dewpoint Setpoint. For MUA units, Unoccupied Dehumidifi cation can
only occur if the unit is confi gured for Night Setback recirculating opera-
tion and has a Space Humidity sensor and a Space Humidity Setpoint.

VCB-X Confi guration

Setpoints for Unit 0001

Configuration

Dehumidification Control

Page 7 of 19

None

Dehumidify in Occupied Vent Mode Only

Dehumidify in Vent Mode Anytime

Dehumidify in All Modes Occupied

Dehumidify in All Modes Anytime

Figure 79: VCB-X Relay Confi guration Screen 7

Setpoints for Unit 0001

Configuration

Reheat Type

Page 8 of 19

None

On/Off HGR Relay

Modulating HGR

Use Unit Heat for Re-Heat

Mod HGR AND Unit Heat

On/Off HGR AND Unit Heat

Figure 80: VCB-X Relay Confi guration Screen 8

Reheat Type

This confi guration option is available if expansion module EM1 has been
installed and confi gured and if Dehumidifi cation has been confi gured.
If you need Reheat in the Dehumidifi cation mode, this screen allows
you to confi gure what kind of reheat will be used. The output(s) will be
staged or modulated to maintain the Active Supply Air Setpoint. Touch
the radio button to select the desired Reheat Type. Default is None.



None—

No Reheat.

 

On/Off HGR Relay—

Single On/Off Reheat stage (Reheat

Relay).

 

Modulating HGR

—Modulating Hot Gas Reheat

(MHGR)

 

Use Unit Heat for Reheat—

Using the unit’s heat as

Reheat when Hot Gas Reheat is not available.

 

Mod HGR AND Unit Heat

—Using MHGR as the 1

st

form of Reheat, supplemented by unit Heat if necessary.

 

On/Off HGR AND Unit Heat

—Using “Reheat Relay”

stage as the 1

st

form of Reheat, supplemented by unit Heat

if

necessary.

NOTE:

This screen will be grayed-out if not using Dehumidifi cation.

Reversing Valve ( Heat Pump Confi guration)

If you are using a Heat Pump, touch the radio button to select the desired
Reversing Valve Signal if your Heat Pump unit activates its reversing
valve during Cooling or Heating operation. Default is None.



None—

Not a Heat Pump and no externally controlled

reversing

valve.

 

Air to Air Heat Pump Fail to Heating—

Air to Air Heat

Pump and Reversing Valve fails to Heating.

 

Air to Air Heat Pump Fail to Cooling—

Air to Air Heat

Pump and Reversing Valve fails to Cooling.

 

Water Source Heat Pump Fail to Heating—

Water

Source Heat Pump and Reversing Valve fails to Heating.

 

Water Source Heat Pump Fail to Cooling—

Water

Source Heat Pump and Reversing Valve fails to Cooling.

Setpoints for Unit 0001

Configuration

Reversing Valve

Page 9 of 19

None

Air to Air Heat Pump Fail to Heating

Air to Air Heat Pump Fail to Cooling

Water Source Heat Pump Fail to Heating

Water Source Heat Pump Fail to Cooling

Figure 81: VCB-X Relay Confi guration Screen 9