VCB-X Controllers

SAT Reset Source

This confi guration option is not available if Single Zone VAV was
selected as the HVAC source. The Supply Air Setpoint can be “auto-
matically” adjusted based on a selected reset source. This screen allows
you to choose this source. Select No Reset for Single Zone VAV units.
Default is No Reset. The available selections are as follows:

 

No Reset

— No SAT Setpoint Reset will occur. The SAT

Setpoints

remain

fi xed.

 

Space Temperature

—The SAT Setpoints will be

adjusted based on the Space Temperature.

 

Outdoor Air

—The SAT Setpoints will be adjusted based

on the Outdoor Air Temperature.

 

Return Air

—The SAT Setpoints will be adjusted based on

the

Return

Air

Temperature.

 

Fan VFD Signal

—The SAT Setpoints will be adjusted

based on the VFD Signal. This is good for Adjusting the

Setpoints based on the building’s load by looking at the

VFD

speed.

NOTE:

This screen will be grayed-out if Single Zone VAV was selected

as the HVAC Mode Enable Source.

Fan Cycle Mode—

Touch the square button to select this item if

you want the HVAC unit’s Supply Fan to only run during

Heating or Cooling Mode. DO NOT select this item if you want

the HVAC unit’s Supply Fan to run continuously while in the

Occupied Mode, regardless of the Heating or Cooling Mode.

Has Head Pressure Control—

Touch the square button to

select this item if you have the EM1 Module installed and

confi gured and if a Head Pressure Sensor is installed for Head
Pressure

Control.

Has Water Side Condenser—

Touch the square button to

select this item if you have the EM1 Module installed and

confi gured and if using a Water Side Condenser.

VCB-X Confi guration

Outdoor Air Temperature

—This is for a 100% Outdoor

Air Unit (MUA) using the Outdoor Air Temperature Sensor to

determine the Heating, Cooling, and Vent Modes of operation.

Dehumidifi cation utilizes an Outdoor Air Dewpoint Setpoint

Supply Air Cooling Only

—This is for a standard

Cooling Only VAV unit with optional Morning Warm Up.

In the Occupied Mode, the unit will be in the Cooling

Mode controlling to the Cooling Supply Air Setpoint.

Return Air Temperature

—Optional recirculating unit

confi guration using the Return Temperature Sensor to

determine the Heating, Cooling, and Vent Modes of

operation.

Space Temp w/ High OA Content

—If it is preferable

to use Space conditions (instead of Outside Air) to control

a 100% or high percentage outdoor air unit, this option

allows tempering of the outdoor air in the Space Vent

Mode of operation to prevent dumping of hot or cold air

into the space.

Setpoints for Unit 0001

Configuration

Static Pressure Control

None

Page 4 of 19

Fan VFD or Single Zone VAV

Bypass Damper

Figure 76: VCB-X Relay Confi guration Screen 4

Setpoints for Unit 0001

Configuration

SAT Reset Source

Page 5 of 19

No Reset

Space Temperature

Outdoor Air

Return Air

Fan VFD Signal

Figure 77: VCB-X Relay Confi guration Screen 5

Setpoints for Unit 0001

Configuration

Use Fan Cycle Mode

Has Head Pressure Control

Has Water Side Condenser

Page 6 of 19

Figure 78: VCB-X Relay Confi guration Screen 6

Static Pressure Control

This confi guration option is available if expansion module EM1 is
installed and confi gured. Default is Fan VFD. The options are:

None

—This unit is not controlling Duct Static Pressure.

Fan VFD or Single Zone VAV

—This unit has a Supply

Fan VFD that modulates to control the Duct Static Pressure.

Bypass Damper

This unit uses a Bypass Damper to

control the Duct Static Pressure.