Vcm, vcm-x & vcb-x controllers, Vcb-x controllers, Vcb-x confi guration – Orion System System Manager TS II In-House User Manual

Page 46: Smts ii technical guide 46, Zone

Advertising
background image

Zone

Zone

VCM, VCM-X & VCB-X Controllers

SMTS II Technical Guide

46

VCB-X Controllers

Heating Type

Touch the radio button to select the desired Heating Type. Modulating
Heat is always initiated fi rst. Default is None.



None

—The unit has no Heat.

 

Staged Control

— On/Off Hot Water or fi xed stage(s) of

Heat.

 

Modulating Control

—Only fully modulating forms of

Heat which would be Modulating Hot Water, Modulating

Steam Heat or Modulating SCR Electric Heat. Does not

include Modulating Gas using the AAON

®

MODGAS-X

Controller.



Mod Gas Control

—Only Modulating Gas Heat controlled

by

the

AAON

®

MODGAS-X Controller.

 

Modulating and Staged Control

—Fully modulating

as the 1

st

form of Heat and Stage(s) of Heat as the 2

nd

form

of

Heat.

 

Mod Gas and Staged Control

—ModGas Heat as the 1

st

form of Heat and Stage(s) of Heat as the 2

nd

form of Heat.

See the VCB-X Controller Field Technical Guide for a more detailed
description of these operations.

NOTE:

If you are using a Heat Pump, this screen will not appear.

Aux Heating Type

If you are using a Heat Pump, touch the radio button to select the desired
Aux Heat option. Default is None.



None

—This unit does not have Heat Pump

Auxiliary

Heat.

 

Staged Control

— This unit has a stage(s) of Auxiliary

Heat. Multiple relays can be confi gured as Aux Heat in

which case the relays will stage up as required.

 

Modulating Control

—This unit has a form of modulating

heat being used as Auxiliary Heat. ModGas cannot be used

as the modulating heat source.

 

Mod Heat AND Staged Heat

—This unit has modulating

heat that will be used as the 1st form of Auxiliary Heat

followed by a stage(s) of Aux Heat.

NOTE:

If you are not using a Heat Pump, this screen will not appear.

Cooling Type

Touch the radio button to select the desired Cooling Type. If your HVAC
unit is equipped with a Digital Compressor, touch the radio button to
select Modulating Control or Modulating and Staged Control. Modulat-
ing Cooling is always initiated fi rst. Default is None.



None

—The unit has no Cooling.

 

Staged Control

— On/Off Chilled Water or fi xed stage(s)

DX Cooling only.

 

Modulating Control

— Modulating Chilled Water or

Digital Scroll Compressors.

 

Modulating and Staged Control

— Digital Scroll

Compressor(s) as the 1

st

form of Cooling and fi xed stage(s)

of Cooling as the 2

nd

form of Cooling.

Digital Compressor—

Touch this square if your HVAC unit is

using a Digital Compressor. Default is No.

VCB-X Confi guration

Setpoints for Unit 0001

Configuration

Heating Type

Page 10 of 19

None

Staged Control

Modulating Control

Mod Gas Control

Modulating and Staged Control

Mod Gas and Staged Control

Figure 82: VCB-X Relay Confi guration Screen 10 - No
Heat Pump

Setpoints for Unit 0001

Configuration

Aux Heating Type

Page 10 of 19

None

Staged Control

Modulating Control

Mod Heat and Staged Heat

Figure 83: VCB-X Relay Confi guration Screen 10 -
Heat Pump

Setpoints for Unit 0001

Configuration

Cooling Type

Page 11 of 19

None

Staged Control

Modulating Control

Modulating and Staged Control

Digital Compressor

Figure 84: VCB-X Relay Confi guration Screen 11

Advertising
This manual is related to the following products: