VCM, VCM-X & VCB-X Controllers

SMTS II Technical Guide

62

VCB-X Controllers

VCB-X Relays Setpoints

Relays Setpoints

Touch the

< Relays>

button to access the Outputs Setpoints

Screens. Touch the radio button next to the desired relay
selection. Choose one relay output from each screen for
Relays 2 through 23 depending on whether you have the

EM1 Module and/or 12 Relay Module installed and confi gured. See
Table 7 on the next page for Relay Defi nitions.

NOTE:

Relay #1 is not confi gurable as it is reserved for the

Supply Air Fan.



Not Used

 

Digital Compressor

 

Cooling Stage

 

Heating Stage

 

Condenser Fan #1

 

Condenser Fan #2

 

Heat Pump Water Valve

 

Heat Pump Compressor

 

Heat Pump Reversing Valve

 

Heat Pump Aux Heat

 

Heat Pump Emergency Heat

 

Mod Heat Enable

 

Mod Cool Enable

 

Morning Warm-Up / Cool-Down

 

Reheat

 

Preheat

 

Low Ambient

 

Exhaust Fan

 

Economizer

 

Heat Wheel

 

Occupied Mode

 

Override Mode

 

Alarm Indicator

Relays

Table 7: User-Confi gurable Relay Outputs

No. Relay Description

Details

1

Digital Compressor

Confi gured for a Digital Compressor.

2

Cooling Stage

Confi gured for each fi xed stage of cooling (except heat pump compressor).

3

Heating Stage

Confi gured for each fi xed stage of heating.

4-5

Condenser #1
Condenser #2

Confi gured for Condenser Fan/Valve operation. This relay(s) will be active anytime the respective
compressors are active, except if the unit is in Heat Pump Defrost Mode.

6

Heat Pump Water Valve

On a Water Source Heat Pump, this relay will be active anytime compressors are active.

7

Heat Pump Compressor

Confi gured for a Fixed Heat Pump Compressor stage.

8

Reversing Valve

Confi gured for the Reversing Valve of a heat pump unit.

9

Aux Heat

Confi gured for a fi xed stage of Aux Heat in a heat pump unit.

10

Emergency Heat

Confi gured for a fi xed stage Emergency Heat in a heat pump unit.

11

Mod Heat Enable

Confi gure if a 0-10 VDC Modulating Heat source needs a relay to enable it.

12

Mod Cool Enable

Confi gure if a 0-10 VDC Modulating Cool source needs a relay to enable it.

13

Morning Warm-Up/
Cool-Down (VAV Boxes)

Confi gure (1) Relay for Morning Warm-Up/Cool-Down when Non-Orion VAV/Zone Controllers are
used.

14

Reheat

Confi gure (1) Relay for On/Off Reheat when used.

15

Pre-Heat

Confi gure for Pre-Heat operation.

16

Low Ambient

Confi gure for Low Ambient operation.

17

Exhaust Fan

Confi gure (1) Relay for enabling exhaust fan when Building Pressure Control is used.

18

Economizer Active

If confi gured, this relay will energize if unit is in Economizer mode and the damper has moved 5%
above its Economizer Minimum Setpoint position.

19

Heat Wheel

Confi gure (1) Relay that turns heat wheel on when in Occupied operation and turns heat wheel off
when in Economizer Mode.

20

Occupied Active

If confi gured, this relay will energize whenever the unit is in the Occupied Mode.

21

Override Active

If confi gured, this relay will energize anytime the space sensor Push-button override is active.

22

Alarm Active

If confi gured, this relay will energize anytime a VCB-X alarm is active.