Vcm & vcm-x controllers, Vcm-x miscellaneous setpoints, Smts ii technical guide 40 – Orion System System Manager TS II In-House User Manual

Page 40

Advertising
background image

VCM & VCM-X Controllers

SMTS II Technical Guide

40

VCM-X Miscellaneous Setpoints

Setpoints for Unit 0102

Space Sensor Offset

Outdoor Sensor Offset

0.0

0.0

Supply Sensor Offset

Return Sensor Offset

0.0

0.0

Miscellaneous

°F

°F

°F

°F

Page 5 of 5

Coil Temperature Offset

0.0

°F

Figure 67: VCM-X Miscellaneous Setpoints Screen 5

Space Sensor Offset

If the Space Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Space Temperature
Sensor reading and a negative value to lower the Sensor reading. High limit
= 100ºF; Low limit = -100ºF; Default = 0ºF.

Supply Sensor Offset

If the Supply Air Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Supply Air Tempera-
ture Sensor reading and a negative value to lower the Sensor reading. High
limit = 100ºF; Low limit = -100ºF; Default = 0ºF.

Return Sensor Offset

If the Return Air Temperature Sensor is reading incorrectly, you can use this
option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Return Air Temperature
Sensor reading and a negative value to lower the Sensor reading. High limit
= 100ºF; Low limit = -100ºF; Default = 0ºF.

Outdoor Sensor Offset

If the Outdoor Air Temperature Sensor is reading incorrectly, you can use
this option to enter an offset temperature to adjust the Sensor’s Temperature.
Enter a positive Sensor Calibration value to raise the Outdoor Air Tem-
perature Sensor reading and a negative value to lower the Sensor reading..
High limit = 100ºF; Low limit = -100ºF; Default = 0ºF.

Coil Temperature Offset

If the Coil Temperature reading needs to be adjusted, enter a positive value
to raise the Coil Temperature reading and a negative value to lower the Coil
Temperature reading. High limit = 30ºF; Low limit = -30ºF; Default = 0ºF.