VCM, VCM-X & VCB-X Controllers

47

VCB-X Controllers

Economizer Control

Touch the radio button to select type of Economizer Control. Default is
None. Touch the square button to allow Economizer Control in Unoc-
cupied Mode. Default is No Economizer Allowed in Unoccupied Mode.



None—

No Economizer being controlled directly by this

controller.

 

Economizer Only—

Economizer being controlled but no

CO

2

control.

 

Economizer with CO2 Reset—

Economizer controlled

but with the ability for CO

2

to reset the Minimum position.

Economizer Allowed in Unoccupied Mode—

Default is

NO.

This

confi guration option is available if Economizer

Control is confi gured.



YES—

You want to use the Economizer as necessary

during Unoccupied Night Setback cooling calls. It will

be utilized just as it would be in the Occupied mode

with the same outdoor enable temperature. The

Economizer will remain closed unless there is

a call to run while in the Unoccupied Mode.



NO—

You want the Economizer to always remain fully

Closed in the Unoccupied mode even if there is a call

to run from a zone or space temp.

Economizer Title 24 Option—

Select this item if your unit has

Title 24 Economizer operation.

VCB-X Confi guration

Economizer Enable Source

This confi guration option is available if the unit was confi gured for
Economizer Control. Touch the radio button from the Economizer En-
able methods listed below that will allow the Economizer to be used as
the fi rst stage of cooling. Default is OA Drybulb.

 

OA Drybulb—

If the Outdoor Air Drybulb temperature is

below the enable setpoint, the Economizer can be used as

the

fi rst stage of cooling.

 

OA Wetbulb ( OA RH sensor needed)—

If the Outside

Air Wetbulb temperature is below the enable setpoint, the

Economizer can be used as the fi rst stage of cooling.

 

OA Dewpoint ( OA RH sensor needed)—

If the Outdoor

Air Dewpoint temperature is below the enable setpoint, the

Economizer can be used as the fi rst stage of cooling.

Building Pressure Control

This confi guration option is available if the EM1 Module has been
installed and confi gured. Touch the radio button to select type of Building
Pressure Control. Default is None.



None—

No Building Pressure Control by this controller.

 

On/Off Control—

If the building pressure rises above

setpoint, a relay confi gured as Exhaust Fan will energize in

order to turn on an On/Off exhaust fan. You must confi gure

one of the output relays as Exhaust Fan.

 

Modulating Control—

If the building pressure rises above

setpoint, a modulating signal will be used to control an

exhaust fan VFD or a modulating damper. A relay

confi gured as Exhaust Fan can be used to enable this device

so that the modulating signal can control it.

 

Reverse Acting OA Damper Control

—Select if reverse

acting Building Pressure Control using the Outdoor Air

Damper is required. If the building pressure falls below

setpoint, the OA Damper (Economizer) signal will be used

to modulate the OA Damper to maintain setpoint.

 

Reverse Acting Supply Fan VFD Control

—Contact

WattMaster Factory regarding this reverse acting Building

Control option. This should not be used in most

applications.

Setpoints for Unit 0001

Configuration

Economizer Control

Page 12 of 19

None

Economizer Only

Economizer with C 2 Reset

Economizer Allowed in Unoccupied Mode

Economizer 24 Option

O

Figure 85: VCB-X Relay Confi guration Screen 12

Setpoints for Unit 0001

Configuration

Economizer Enable Source

Page 13 of 19

OA Drybulb

OA Wetbulb { Requires OA Humidity Sensor }

OA Dewpoint { Requires OA Humidity Sensor }

Figure 86: VCB-X Relay Confi guration Screen 13

Setpoints for Unit 0001

Configuration

Building Pressure Control

Page 14 of 19

None

On/Off Control

Modulating Control

Reverse Acting O/A Damper Control

Reverse Acting Supply Fan VFD Control

Figure 87: VCB-X Relay Confi guration Screen 14