Remko heat pump manager – REMKO Multi-talent User Manual

Page 16

Advertising
background image

REMKO HEAT PUMP MANAGER

Hot water

Designation

Value range

Factory setting

Description

1xhot water

On/Off

Off

The tank is only enabled for a one time loading
(= ON) (e.g. for showering outside of hot water times).
Loading only begins if the T-WW 1 target temperature has
been undercut by the amount of the switching hysteresis
(see specialist

hot water

hysteresis WW)

.

.

T-WW 1 target

10°C-70°C

50°C

Setting the desired hot water temperatures for the hot water
programme's 1st, 2nd and 3rd enabling times (see time
programme

hot water).

T-WW 2 target

10°C-70°C

50°C

T-WW 3 target

10°C-70°C

50°C

BoB value

0.0K-70.0K

0.0K

Power saving function for solar or solid fuel boiler (operation
without burner).
The burner is activated if the current hot water temperature
in the amount of the set value here + switching hysteresis
(see specialist

hot water

hysteresis WW) has fallen

below the set hot water target temperature.

Circ with WW prog

On/Off

Off

Activating the circulation pump.
The circulation pump runs when hot water is enabled
(= ON), the circulation programme (see time programme

circulation programme) has no impact.

Anti-legionella

On/Off

Off

Activating the anti-legionella function.
With every 20th heating or at least once a week (on
Saturdays at 01:00) the tank is warmed to 65°C (= ON).
It is possible to set a separate anti-legionella function e.g.
by means of the 3rd hot water enabling time (see time
programme

hot water).

Be submitted to activation of anti-legionella program must
usually electric heating thermostat to 65 °C.

Heating circuit 1/2

Designation

Value range

Factory setting

Description

Operating mode

----

Standby

Cooling

Automatic 1+2

Summer

Heating

Reduction

Service

----

Setting the operating mode for the respective heating circuit.

!

CAUTION

If an operating mode is set here outside of "----", this
operating mode will always apply for the respective heating
circuit regardless of the operating mode setting in the main
menu. This setting possibility is intended for the use of a
remote control.

T-room target 1

5.0°C-40.0°C

20.0°C

Setting of the desired room temperature for the 1st, 2nd
and 3rd enabling times of the active heating programme in
automatic 1/2 operating mode. A setting other than 20 °C
causes a parallel shift of the heat curve on page 6.

T-room target 2

5.0°C-40.0°C

20.0°C

T-room target 3

5.0°C-40.0°C

20.0°C

T-reduction

5.0°C-40.0°C

15.0°C

Setting the desired room temperature during night reduction
(time between heating periods, see time programme

heating circuit 1/2 prog 1/2).

Adjustable values can vary depending on the function selected for the heating circuit.

Level 4 - USER - Description of parameters and settings - continued