Remko heat pump manager – REMKO Multi-talent User Manual

Page 38

Advertising
background image

REMKO HEAT PUMP MANAGER

Designation

Value range

Factory setting

Description

Hysteresis WW

3. 0 K - 3 0. 0 K

5. 0 K

Setting the hot water hysteresis.

Water heating starts if the temperature in the hot water tank
(sensor F-6) falls below the target temperature (see user

hot water

T-WW target) by the temperature set here.

Water heating ends if the tank reaches the set target
temperature
(in the anti-legionella mode the target temperature is set to
65°C, see user

hot water

anti-legionella).

WW lag

0 0 - 3 0

0 1

Setting the pump lag period.


The pump lag period (5 min.) is extended by the value set
here.

The indoor unit's charge pump continues to run for
another 5 minutes after the heat pump has been shut off
(independent of the period set here).
The lag period is interrupted if there is a demand for heat in
a heating circuit.
An activated charge pump lock can likewise lead to an
interruption of the lag function.

TH inlet

On / Off

Off

Activating the water heating by means of thermostat or sensor.

On (water heating by means of thermostat)
In the event of a short circuit, water heating is started at the
tank sensor's connection terminals. It ends if the short circuit
has been corrected.

Off (water heating by means of tank sensor).

Thermal function

On / Off

Off

Activating the aligned target temperature.

The target temperature during water heating is arrived at by
adding the current tank temperature [sensor 6] to T-WE WW.

Charging

On / Off

Off

Activating the charging function
(only possible with sensor 12 = T-WW U).

Water heating with activation of this function (charging =
ON) is not ended until the sensor F 12 (not F 6) has reached
the warm water target temperature.

Hot water - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

38