REMKO HEAT PUMP MANAGER

0-10V I/O

Designation

Value range

Factory setting

Description

SPG curve

00-11

11

Selection for the voltage curves for the configuration of the
voltage in and output (default voltage curve or the freely
adjustable curve 11).

Curve 11-U1

0.0 V-10.0 V

2.0 V

An individual curve can be defined with the parameters U1,
U2, T1, T2 und UA.

U = voltage.

T = temperature.

UA = heating appliance Off.
Beginning at this voltage, the WE is shut off. UA must lie
outside of the valid voltage values.

U1 and T1 = point 1 on the voltage curve.

U2 and T2 = point 2 on the voltage curve.

The line between the two limit points defines the voltage
curve.

Curve 11-U2

0.0 V-10.0 V

10.0 V

Curve 11-T1

0,0-120,0

10,0

Curve 11-T2

0,0-120,0

100,0

Curve 11-UA

0.0V-10.0 V

0.0 V

The outdoor unit is controlled with a 0-10V signal (conversion of the target output or modulation depth).
The factory settings for the following parameters may only be carried out in coordination with REMKO's product
management!

Screed

Designation

Value range

Factory setting

Description

Screed

On/Off

Off

Activating the screed programme (only for 2 mixing circuits).

When started the programme shuts down the set supply
temperatures. The integrated mixer circuits regulate in ac-
cordance with the set supply temperature. The heat pump
makes
this temperature available independent of the set operat-
ing mode. In the standard display, this is identified with the
entry "Screed" and the display of the currently valid supply
temperature.

The screed programme starts at 00:00 with the set supply
temperature from "Day 1" (the start day is not counted)
and switches to each subsequent day at 00:00.
The current day is identified in the screed programme with
an "x".

Following interruption/ending of the function, the controller
continues to heat in the currently set operating mode.

Screed programme

Day 1-28

10°C-60°C/----

Day 1-3: 25°C
Day 4-7: 55°C
Day 8: 25°C
Day 9: 40°C
Day 10-19: 55°C
Day 20: 40°C
Day 21: 25°C
Day 22-28: ----

Setting the desired temperatures for the respective days.

The input "----" ends the programme (even during the
operation for the following day).

Level 4 - SPECIALIST - Description of parameters and settings - continued

The screed program may be conducted only in conjunction with the two heat sources. The bivalence is highly enforce, if necessary.

!

CAUTION