Remko heat pump manager – REMKO Multi-talent User Manual

Page 40

Advertising
background image

REMKO HEAT PUMP MANAGER

Designation

Value range

Factory setting

Description

Operation HCP

Standard

Heating limits

only time prog

Continuous

operation

Standard

Setting the operating mode for the heating circuit pumps.

The pumps are shut off if there is no heating requirement.

At the same time the mixer of the heating circuit closes.

Standard

- with weather-controlled target temperature regulation

through heating curve:

Pump OFF if the current outside temperature

[Sensor 09] has become warmer than the set temperature

and by the activation of the operating mode

T-room target temperature.

- with room-guided regulation (only active in combination

with a remote control)

Pump OFF if the current room temperature has become

more than 1K warmer than the set room target

temperature.

Heating limits

The pump is switched analogously to the set heating

limits (see User

Heating circuit 1/2

Heat limit day/Heat limit night)

Only time programme

Pump is switched according to the heating programme

(see User

Time programme

Heat circuit 1Prog

1/2 and/or

Heat circuit 2 Prog 1/2

Continuous operation.

The pump runs continuously for 24h.

Mixer Open

5,0-25,0

7,0

Setting the speed with which the mixer opens in the event

of a control deviation (mixer dynamic opening).

The control deviation is entered in Kelvin where the mixer

opens without interruption.

Small values lead to fast operation of the mixer and can lead

to vibrations.

Mixer Closed

5,0-25,0

7,0

Setting the speed with which the mixer closes in the event of

a control deviation (mixer dynamic closing).

The control deviation is entered in Kelvin where the mixer

closes without interruption.

Small values lead to fast operation of the mixer and can lead

to vibrations.

Max T-supply

10.0°C-110.0°C

55.0°C

Setting the maximum supply temperature for the selected

heating circuit.

The calculated supply target temperature for the heating

circuit is limited by the set maximum supply temperature

(overheating protection).

The heating circuit pump for the direct heating circuit is only

switched off if the [sensor 08] exceeds the temperature set

here by 8K.

The heating circuit pump switches on again if the

temperature [sensor 08] falls below the temperature

(Max T-supply+5K).

Heating circuit 1/2-continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

40

Advertising