Remko heat pump manager – REMKO Multi-talent User Manual

Page 32

Advertising
background image

REMKO HEAT PUMP MANAGER

Cascade

Designation

Value range

Factory setting

Description

WE found

1-3---/x-x---

1-3/x-x

Display of the heating appliance automatically logged by the
BUS with BUS identifier (heat generator-number).

The displayed "x" indicates that the heating appliance has
answered the BUS.

Output/level

WE 1-WE 8

WE internal

WE 1 level 1 = 50
WE 2 level 1 = 01
WE 3 level 1 = 01

Display of the heat generator-number and level.

For "---" the level for the heat generator does not exist.

Following a restart or new configuration, the controller
searches in the BUS systems for heating appliances. In this
period (approx. 1 min.) the output cannot yet be entered
manually.
If a heating appliance answers indicating the output, this
output will automatically be entered in the list.
If a WE answers without indicating the output, the output is
entered in the list with 15KW.
(this value can then be corrected manually).

BUS scan

On/Off

Off

Search for heating appliances in the BUS.

If the displayed configuration is correct, it can be saved with
"OK". All current values are then overwritten.

Min. Mod Cascade

00-100 %

00 %

If the cascade controller calculates a total modulation depth
greater than nil and smaller than Min. Mod Cascade, total
modulation depth will set to the value set here (minimum
modulation depth).
At the same time, clock inhibition will be set to 10 sec.

WW-WE

00-08

00

Water heating by means of collector (00).

The Number of heat generators in the cascade which for
water heating are hydraulically decoupled from the cascade
(01-08).

System deviation

Display of the current collector system deviation (difference
between target temperature and current temperature
[sensor 08]).

Output target

0-100 %

Display of the currently required total system output
(corresponds with the calculated target value in the
controller).

Remaining idle time

Remainder (min.)

Display of the currently remaining idle time (not until "0"
can the next heat generator be put into operation).

Max T-WE

50.0°C-110.0°C

72.0°C

Setting the maximum heating appliance temperature.

The heat generators shut off/modulate themselves down
independently if they have not reached the temperature
set here (protects the cascade's individual heat generators
against overheating and prevents the STB from triggering).

The heat generators switch on again if the set temperature is
undercut by 5K.

The temperature set here should be higher than the
maximum collector temperature Max T-collector
(see specialist

heating appliances).

Level 4 - SPECIALIST - Description of parameters and settings - continued

32

Advertising