Remko heat pump manager – REMKO Multi-talent User Manual

Page 26

Advertising
background image

REMKO HEAT PUMP MANAGER

Configuration - continued

Designation

Value range

Factory setting

Description

System selection

----/01-12

01

With the selection of the system, one of the 12 basic hy-

draulic configurations described below is loaded; they are

saved in the heat pump manager. With this pre-configura-

tion, the additional values to be set are minimised for the

installer.

The basic hydraulic configurations, including parameter val-

ues, can be found in the appendix of this manual..

01 = Basic hydraulics for the functions “Heating and hot
water”, single energy-source mode, 1 supplemental electric
heating, bivalence point -5°C

02 = only heating version, single energy-source mode,

2 levels for supplemental electric heating, bivalence point -5°C.

03 = only heating version, bivalent mode, boiler + option

for 1 supplemental electric heating, bivalence point -3°C.

04 = only heating version, bivalent mode, solid fuel boiler

+ option for supplemental electric

Supplemental heating, bivalence point -3°C.

05 = only heating version, single energy-source mode,

1 supplemental electric heating, solar system, bivalence point -5°C.

06 = only heating/cooling version, single energy-source

mode, 1 supplemental electric heating, bivalence point -5°C.

07 = only heating/cooling version, single energy-source

mode, 1 supplemental electric heating, solar system,

bivalence point -5°C.

08 = only heating version, single energy-source mode,

2 levels for supplemental electric heating, solar system,

bivalence point -5°C.

09 = only heating version, bivalent mode + option for 1

supplemental electric heating, solar system, bivalence point -3°C.

10 = only heating/cooling version, bivalent mode,

bivalence point -3°C

11 = heating/cooling version, bivalent mode, solar system,

bivalence point -3°C

12 = heating/cooling version, bivalent mode with solid fuel +

option for 1 supplemental electric heating, bivalence point -3°C

There is no change for "----"

Notice: The selections of the system 02,03,04,05,08 and 09 is

are only for heat pumps CMF 80 and CMF 140..

Regulator type

00-06

06

Setting the regulation type for the system.
00 = No heating appliance (mixer expansion).
01 = Single stage heat generator (switching).
02 = Single stage (modulating).
03 = Two stage heat generator (switching).
04 = Two individual heat generator (switching).
05 = Multi-level switching (cascade over BUS).
06 = Multi-level modulating (cascade over BUS).

WE 1 type

(Output A6

enable or demand

heat pump)

00-09

07

00 = Relay has no function.
01 = Switch on heat generator.
07 = Switch on heat pump.
08 = Switch on cooling 1.
09 = Switch on cooling 2.

Level 4 - SPECIALIST - Description of parameters and settings - continued

26

Advertising