REMKO Multi-talent User Manual

Page 31

Advertising
background image

Designation

Value range

Factory setting

Description

Hyst burner 2

2.0K-20.0K

2.0K

Only for two stage burners or solid material integration.

Setting the hysteresis for the charge pump (solid material
integration) or the 2nd burner

Gradient

On/Off

Off

Activation or deactivation of the gradient-based algorithm.
At „OFF“, the shut-off of the heat pump is carried out by
the target value and the hysteresis.
This function is only assigned to heat generator 1, in other
words the heat pump, and must be set to OFF.

Max reduction

1.0K-20.0K

1.0K

Setting the value to determine the earliest shut-off point
with the gradient-based algorithm activated.

The earliest shut-off point is the difference between the
maximum heating appliance temperature Max T-WE
(see specialist cascade) and the value set here.

Dyn shut-off

0.5K/min.-10K/

min.

2.0K/min.

Load dependent, early shut-off of the heat generator by the
the temperature increase gradients [K/min].

If the heat generator reaches or exceeds the gradient set
here, the heat generator will be switched off at the earliest
dynamic shut-off point (difference between Max T-WE and
Max reduction).

At a low temperature increase, the shut-off point will be in-
creased linearly up to Max T-WE.

WE cooling function

On/Off

Off

Activating the emergency cooling for the heat generator.

T-WE cold start

30.0°C-120.0°C

95.0°C

Setting the maximum temperature for the heating appliance
(Cooling start temperature).

If emergency cooling for the heating appliance has been ac-
tivated (heat generator cooling function = ON), the heating
circuits will then be taken with
Max T-supply (see specialist

heating circuit 1/2) into

operation (if emergency cooling is permitted in the heating
circuit), as soon as the temperature set here has been ex-
ceeded by one of the heating appliances.

Emergency cooling is ended if the start temperature T-WE
cold start is undercut by 5K.

Heating appliances - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

31

Advertising