Configuration - continued

Designation

Value range

Factory setting

Description

WE BUS

00-05

05

00 = Relay (switching heat generator).

01 = CAN-BUS (cascade switching).

02 = eBUS (heat generator without temperature controller,
default modulation depth, cascade modulating).

03 = eBUS (heat generator with temperature controller,
default target temperature T-WE target).

04 = 0-10V (default target temperature T-WE target,
burner relays are controlled in parallel).
Only for regulation type 01, 02, 03, 07.
Sensor 08 must be connected.

05 = 0-10V (default modulation depth).
Only for regulation type 02 or 06.
T-collector [sensor 08] must be connected.

WE 2 type

(Output A7

enable cooling)

00-22

08

Not active for heat generator 1 with two stage burner.

00 = no second heat generator.

01 = Single stage heat generator (switching).

07 = Heat pump.

08 = Cooling 1.

09 = Cooling 2.

20 = Solid fuel boiler (supplemental not controllable heat

generator).

21 = Collector pump

22 = Pump for heat generator 1 (e.g. supplemental heat

generator for cascades).

WE 2 tank

00-03

00

Only active if heat generator 2 type as solid fuel boiler was

selected.

Start-up release:

ON: T-WE 2 > Min T-WE 2.

OFF: T-WE 2 < [Min T-WE 2-5K].

00 = Heating in countercurrent with collector (no tank)

[sensor 08].

ON: T-WE 2 > [T-collector+Hyst burner 2+5K].

OFF: T-WE 2 < [T-collector+Hyst burner 2].

01 = Heating in countercurrent with buffer tank [sensors

01, 03].

ON: T-WE 2 > [T-buffer O+Hyst burner 2+5K].

OFF: T-WE 2 < [T-buffer+Hyst burner 2].

02 = Heating in countercurrent with warm water tank

[sensor 06].

ON: T-WE 2 > [T-WW+Hyst burner 2+5K].

OFF: T-WE 2 > [T-WW+Hyst burner 2].

03 = Heating in countercurrent with tank 3 (swimming

pool) [sensor 15].

ON: T-WE 2 > [T-tank 3+Hyst burner 2+5K].

OFF: T-WE 2 < [T-tank 3+Hyst burner 2].

Level 4 - SPECIALIST - Description of parameters and settings - continued