Remko heat pump manager – REMKO Multi-talent User Manual

Page 28

Advertising
background image

REMKO HEAT PUMP MANAGER

Designation

Value range

Factory setting

Description

WE 2 tank

(continued)

00-03

00

Switching characteristics:

The pump switches on if the temperature of the solid fuel
boiler T-WE 2 exceeds the temperature of the reference sen-
sor [sensor 12] in the amount of the hysteresis [Hyst burner
2+5K].

It shuts off if the temperature T-WE 2 falls below this

switch on temperature by 5K,

Start-up release:

It shuts off if the temperature for the solid fuel boiler T-WE 2 falls
below the temperature limit Min T-WE 2 (see specialist

heat-

ing appliance) by 5K.

The pump is enabled again if the tempera-

ture T-WE 2 rises above the set temperature limit Min T-WE 2.

WE 3 type

(Output A8

enable 2nd heating

appliance)

00-09

01

00 = No third heating appliance (multi-function MF 1).

01 = Single stage heating appliance (switching).

07 = Heat pump.

08 = Cooling 1.

09 = Cooling 2.

WE 4 type

(Output A9

Charging pump

indoor unit)

00-09

00

00 = No fourth heating appliance (multi-function MF 2).

01 = Single stage heat generator (switching).

07 = Heat pump.

08 = Cooling 1.

09 = Cooling 2.

Buffer type

0 0 - 0 2

0 0

Setting the tank type for the heating buffer.

00 = no buffer tank for heating operation.

01 = Buffer tank for heating operation [sensors 02, 03].
The activation of the heat generator 1 takes place with ref-
erence to sensor buffer top [sensor 03].
The charge pump lock impacts the sensor
Buffer top.
WW-charge pump ON: Buffer top > T-WW+5K hysteresis.
WW-charge pump ON: Buffer top < T-WW.

02 = Combination tank for heating and hot water operation.
The activation of the heat generator 1 takes place with ref-
erence to sensor buffer middle [sensor 02].
WW-charge pump ON: T-collector > T-WW+5K hysteresis.
WW-charge pump ON: T-collector < T-WW.

Configuration - continued

Level 4 - SPECIALIST - Description of parameters and settings - continued

28

Advertising